1
60
TROUBLESHOOTING
Alarm Code
dd
Incorrect Wiring Among Indoor Units
This alarm code is indicated only when remote control switch PC-2H2 is used being connected to indoor
unit.
This alarm occurs in the case of incorrect connection like that TL terminal is connected to Vc terminal as
below when indoor units are wired.
The unit No. and unit code are as
below regardless of the indoor unit.
Unit No.
00
Cycle System
00
Unit Code
E00
Is wiring among indoor units
right?
No
Repair the wiring among
indoor units.
Yes
Turn off the main powerswitch
and cut the wire JP4 at remote
control switch, then turn on the
main power switch again.
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Wiring Trouble
Incorrect Wiring
Check the wiring No.
Repair the wiring
Incorrect
Wiring
Remote
Control
Switch
Remote Control
Switch (yellow)
(Blue)
(yellow)
(Blue)
(yellow)