1
TROUBLESHOOTING
21
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Clogging of Heat
Exchanger?
Remove clogging.
Check for dust on air filter
Remove dust.
Check for any obstacles at
inlet or outlet of outlet of
heat exchanger.
Remove obstacles.
Check the service space.
Secure service space.
Insufficient Air Flow to Heat
Exchanger (Outdoor Heat
Exchanger during Cooling
Operation or Indoor Heat
Exchanger during Heating
Operation)
Check for speed.
(Outdoor Fan: Cooling /
Indoor Fan: Heating)
Replace fan motor if faulty.
Disconnected of
Connector
Repair looseness or
reconnect connector.
Expansion Valve Trouble
Fully opened and locked.
(see page 1-93)
Replace expansion valve.
Calculate heat load.
Reduce heat load or use a
bigger unit.
Check for hot air near the
ceiling (Heating).
Make good circulation.
Check for short circuited
air (Heating).
Remove short-circuited
air.
Excessively High Temp.
Air to Indoor Unit Heat
Exchanger
Check for other heat
source.
Remove heat source.
Faulty
Pressure
Switch
Measure discharge pressure.
Check continuity after
decreasing of pressure.
Replace it if faulty.
Insufficient
Contacting
Measure resistance by
tester.
Repair looseness.
Replace connector.
Activation of
High Pressure
Switch due to
Excessively
High Discharge
Pressure
Faulty High
Pressure
Switch
Incorrect
Connection
Check connections.
Repair connections.
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...