1
TROUBLESHOOTING
9
1.1.6
ABNORMAL TRANSMISSION BETWEEN REMOTE CONTROL SWITCH AND INDOOR UNIT
n
”RUN” Lamp on Remote Control Switch:
Flickering every 2 seconds
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Disconnection or insufficient Contacting of Remote
Control Cable
Check cable and
connections
Repair cable or connect it
Incorrect Wiring Connection (Incorrect Polarity)
Check wiring and
connections
Repairing
Failure of Remote Control Switch
Check it by self-check
mode *1)
Replace it if remote control
switch is faulty.
Disconnected Wire to PCB
Check connectors
Correctly connect Wires
Failure of PCB
(In Indoor Unit
and Remote
Control Switch)
Failure of PCB
Check it by self-check
mode *2)
Replace PCB if failed
*1): Refer to Item 1.3.2.
*2): Refer to Item 1.3.1.
*3): This phenomenon occurs when the system is newly
installed and is started within 5 minutes after power supply,
since automatic setting of unit No. is performed during this
period.