1
TROUBLESHOOTING
11
1.1.7 ABNORMALITIES OF DEVICES (Cont.)
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
The Comp.
does not Stop
or Start even if
the Setting
temperature on
LCD is
Changed *3)
Incorrect Optional Setting
Check Setting Condition of
"Remote Control
Thermostat" by Optional
Setting
Setting and Control:
"00": Control by Indoor
Thermistor for
Suction Air
"01": Control by
Thermostat of
Remote Control
Switch
"02": Control by Average
Value of Indoor
Thermistor for
Suction Air and
Thermostat of
Remote Control
Switch
In case that thermostat of
remote control switch is
not used, set at 00".
*1): Refer to Item 1.3.1~1.3.4.
*2): Refer to Item 1.3.1.
*3): Even if controllers are normal, the compressor does not
operate under the followings conditions:
1. Indoor Air Temp. is lower than 21°C or Outdoor Air
Temp. is lower than -5°C during cooling operation.
2. Indoor Air Temp. is higher than 30°C or Outdoor Air
Temp. is higher than 23°C during heating operation.
3. When a cooling (or heating) operation signal is given
to the outdoor unit and a different mode as heating (or
cooling) operation signal is given to indoor units.
4. When an emergency stop signal is given to outdoor
unit.
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...