1
TROUBLESHOOTING
63
n
CONTENTS OF CHECK MODE 1
The next indication is shown by pressing the part
}
of
"TEMP" switch. If the part
~
of "TEMP" switch is pressed,
the previous indication is shown.
7HPSHUDWXUHLQGLFDWLRQ
b1 22
1
Indoor Unit Temp.
Setting (°C)
b2 20
2
Indoor Unit
Intake Air Temp.
at Thermistor (°C)
b3 55
3
Indoor Unit
Discharge Air Temp.
at Thermistor (°C)
b4 20
4
Indoor Unit Heat
Exchanger Liquid pipe
Temp. (°C)
b5 25
5
Temperature at
Remote Sensor (°C)
b6 10
6
Outdoor Unit Ambient
Temp. (°C)
b7 25
7
Indoor Unit Heat
Exchanger Gas Pipe
Temp. (°C)
b8 02
8
Outdoor Unit
Evaporating Temp.
during Heating (°C)
b9 --
9
Control Information
bA 41
10
Discharge Gas Temp.
at the Top of Comp.
Chamber (°C)
to next page
This indicates the internal information for the remote control switch.
In case of SET-FREE, this indication shows the operating
compressor quantity.
In case that temperature is higher than 100 °C, two digits blinks.
(Ex.)
During more than one compressors operation, average
temperature of two compressors is indicated
In case that temperature is higher than 126°C, "
126
" is always
shown
Normal
Abnormal
. . .
Temperature displayed
– –
129
(Thermistor Open circuited
or PCB defected)
(Temp. for Top of Comp.)
FF
or
(Thermistor Open circuited
or PCB defected)
255
or
127
or
(Temp. for Top of Comp.)
Indication of Category Code
Indication of Temperature, etc
See 1.3.1 Self-Checking of PCB’s
using Remote Control Switch" in pages 1-82,83
This is indicated only when a remote sensor is connected.
The indication of "--" is normally indicated.
RPK series can not connect a remote sensor.
Therefore, indication is "--".
NOTE: During transient period such as starting
time, etc. "
--
" may be indiated for a limited time
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...