1
80
TROUBLESHOOTING
b. Inverter Printed Circuit Board: PCB3
*Dip Switch and LED Functions on Outdoor Unit Inverter Printed Circuit Board
Switch Name
DSW1
Function
21
2))
Normal: No.1 and No.2 of DSW1 are OFF.
Emergency Operation or Troubleshooting:
No.1 of DSW1 is ON
No.2 of DSW1 is OFF
The above setting aims not to trip even if the CT detects 0A.
Name of Printed Circuit Board
Function
LED1 (Red)
This indicates the state of transmission.
Flickering: Normal Transmission
Activated or Deactivated: Abnormality in Transmission Circuit
* LED2 (Red)
This indicates the voltage between both terminal of capacitor CB1 and CB2
for inverter part.
Activated: The voltage between both terminals of capacitor, CB is 50V ±
20V or greater.
Deactivated: The voltage between both terminals of capacitor, CB is 50V
±20V or smaller.
*: Applied to the following products;
RAS-5FSG/FS3 (After Manufacturing # U4MV0197)
RAS-8~20FSG/FS3 (After Manufacturing # U4NG1002)