4
OPTIONAL FUNCTION
3
Table 4. 1 Specifications on Required Components for
(1)
~
(4) Functions:
Component
Manufacturer or
Specifications
Remarks
Auxiliary Relay (X1, X2)
OMRON Mini Power Relay
Model: MY1F or Equivalent
Changeover Switch (SS2, SS3)
Manual Type
Voltage
220V or 240V
3P Connector Cord
Optional Part PCC-1
(Able to Connect JST
Connector XHP -3)
Five Cords with
Connectors as one
set
Low Voltage
0.3mm²
less than 24V
Cord (Inside
of Unit)
220V/240V Class
0.5
~
0.75mm²
Low Voltage
0.3
~
0.75mm²
less than 24V
Cord (Outside
of Unit
220V/240V Class
2mm²
NOTE:
Make the wires CN4 as short as possible. Do not install
the wires along the 200-400V power line. Separately
install them at a distance of more than 30cm.
(Intersecting as applicable.) If the wires are installed
along the power line, put the wires in a metal tube and
connect a wire to an end for grounding. The maximum
wiring length is 70m. In the case that this function is
used, it is recommended that safety devices such as
electric leakage breaker or smoke detector, etc. be
used.
4.1.2.
POWER SUPPLY ON/OFF 1 (AUTOMATIC
OPERATION WHEN POWER SUPPLY ON)
Set the dip switch on the PCB for the indoor unit as shown
in the figure below to start and stop the system
automatically according to the power supply ON/OFF.
When this function is utilized in the condition that there is
no person to operate the unit, make the system with
monitoring for disaster prevention.
Ö
CAUTION:
Turn OFF the power source before setting the dip
switch.
NOTE:
The unit is started and stopped according to the power
supply ON/OFF due to the power failure. When the
power failure is occurred during stoppage by the remote
control switch operation, the unit is started again
automatically after the power supply is recovered.
4.1.3.
POWER SUPPLY ON/OFF 2 (RESTARTING
FUNCTION AFTER POWER FAILURE)
Set the dip switch on the PCB for the indoor unit as shown
in the figure below to restart the system automatically even
if power failure continues for more than 2 seconds. The
standard setting provides automatic restarting in less than
2 seconds affer a power failure. The compressor starts in 2
seconds after a 3 minute time guard after power failure.
Ö
CAUTION:
Turn OFF the power source before setting the dip
switch.
NOTE:
The system does not start if the system is stopped
before power failure.
4.1.4.
CONTROL BY FIELD-SUPPLIED ROOM
THERMOSTAT
In the case that a field-supplied room thermostat instead of
the inlet thermistor of the indoor unit is used, connect wires
as shown below. The required parts are shown in Table 4.
2
Field-Supplied Room Thermostat:
Ö
CAUTION:
Turn OFF the power source before setting the dip
switch.
Set No.5 at ON Side
Indoor Unit PCB
Set No.7 at ON Side
Indoor Unit PCB
3P Connector
Thermostat
Temperature
Increase
Indoor Unit
Set No.3 at ON Side
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...