TROUBLESHOOTING
23
Alarm Code
03
Abnormal Transmitting between Indoor Units and Outdoor Unit
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm is indicated when abnormality is maintained for 3 minutes after normal transmitting between
indoor units and outdoor unit, and also abnormality is maintained for 30 seconds after the micro-computer is
automatically reset.
The alarm is indicated when the abnormal transmitting is maintained for 30 seconds from starting of the
outdoor unit.
Investigate the cause of overcurrent and take necessary action when fuses are melted or the breaker for
the outdoor unit are activated.
(See next page)
Note from next page:
*1) In case that terminal resistance (DSW10-1P) is OFF when H-Link Connection is performed.
Set the terminal resistance to ON when CN2 is removed.
Set the terminal resistance to OFF when CN2 is reconnected.
Check Item
Power Supply
FastonTerminal
380-415V 50Hz
between R1 and N
*2) PCB1 factory Setting for Non-pole Transmitting
item
Setting Position
SW1
Left side (New transmission side)
JP1
Short Circuit
CN2
Transmission Wire Connecting
CN18
NBon-Occupied
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...