TROUBLESHOOTING
n
Protection Control Code on 7-Segment Display
1. The protection control indication can be seen on
7-segments when a protection control is activated.
2. The 7segment continues ON while function is working,
and goes out when released.
3. When several protection control are activated, code
number with higher priority will be indicated (see besides
for the priority order).
n
Higher priority is given to protection control related to
frequency control than the other.
<Priority Order>
Pressure Ratio Control
High-Pressure Rise Protection
Current Protection
Discharge Gas Temperature Rise Protection
Low-Pressure Fall Protection
Reversing Valve Switching Control (For 16,
20HP)
High-Pressure Fall Protection
Oil Return Control
n
In relation to retry control, the latest retrial will be
indicated unless a protection control related to frequency
control is indicated.
Code
Protection Control
Code
Protection Control
p 0 1
Pressure Ratio Control (*)
p 1 1
Pressure Ratio Falling Retry
p 0 2
High-Pressure Rise
Protection (*)
p 1 2
Low-Pressure Rising Retry
p 0 3
Current Protection (*)
p 1 3
High-Pressure Rising Retry
p 0 5
Discharge Gas Temperature
Rise Protection (*)
p 1 4
Over Current Retry of
Constant Compressor
p 0 6
Low-Pressure Fall Protection
p 1 5
Vacuum/Discharge Gas
Temperature Rising Retry
p 0 7
4-Way Valve Switching
Control (For 16, 20HP)
p 1 6
Discharge Gas SUPERHEAT
Falling Retry
p 0 8
Oil Return Control
p 1 7
Inverter Trip Retry
p 0 9
High-Pressure
Fall Protection
p 1 8
Voltage Falling/Excessive
Voltage Retry
In the case that restricted control is activated, c is indicated
instead of 0 (*mark)
Retry indication continues for 30 minutes unless a
protection control is indicated.
Retry indication disappears if the stop signal comes from
all rooms.
Note: The protection control code being indicated on
7–segment display is changed to an alarm code
when the abnormal operation occurs. Also, the
same alarm code is indicated on the remote control
switch.
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...