5
4
FIELD WORK INSTRUCTION
5.6.
SELECT GUIDE OF DRAIN PIPE FOR INDOOR UNIT
n
Selecting Method of Drain Pipe Diameter
1. Calculation of Drain Flow Volume
Calculate from that the drain flow volume is
approximately 3 (I/hr) per 1HP of the indoor unit
nominal capacity.
For Example:
Common drain pipe for four 2HP indoor units and four
2.5HP indoor units.
Total Horse Power of
Indoor Unit
4
2HP + 4
2.5 HP=18HP
Total Drain Flow Volume
18HP
3 (l/hr
HP) =
54 (l/hr)
2. Select Drain Pipe from Table A and B
Horizontal Common Pipe
with Slope 1/50
VP30 for above Example
Horizontal Common Pipe
with Slope 1/100
VP30 for above Example
Vertical Common Pipe
VP30 for above Example
Table A. Permissible Drain Flow Volume of Horizontal Vinyl
Pipe
Permissible Flow Volume (I/hr]
JIS Symbol
Inner Diameter
(mm)
Slope=1/50
Slope=1/100
VP20
20
39
27
VP25
25
70
50
VP30
31
125
88
VP40
40
247
175
VP50
51
472
334
NOTE
VP20 and VP25: Not Applicable to Common Pipe
VP30, 40 and 50: Applicable to Common Pipe
Table B. Permissible Drain Flow Volume of Vertical Vinyl
Pipe
JIS Symbol
Inner Diameter
(mm)
Permissible Flow Volume (I/hr]
VP20
20
220
VP25
25
410
VP30
31
730
VP40
40
1400
VP50
51
2760
VP65
67
5710
VP75
77
8280
NOTE
VP20, 25 and 30: Not Applicable to Common Pipe
VP40, 50, 65 and 75: Applicable to Common Pipe
5.7.
CAUTION ON REFRIGERANT LEAKAGE
n
Maximum Permissible Concentration of H(C)FC Gas
The refrigerant R407C (or R22), charged in the SET-FREE
FSG system, is an incombustible and non-toxic gas.
However, if leakage occurs and gas fills a room, it may
cause suffocation.
The maximum permissible concentration of H(C)FC gas,
R407C in air is 0.3 kg/m³ according to the refrigeration and
air conditioning facility standard (KHK S 0010) by the KHK
(High Pressure Gas Protection Association) Japan.
Therefore, some effective measure must be taken to lower
the R407C concentration in air below 0.3 kg/m³, in case of
leakage.
n
Calculation of Refrigerant Concentration
1.
Calculate the total quantity of refrigerant R (kg)
charged in the system connecting all the indoor units
of rooms to be air-conditioned.
2.
Calculate the room Volume V (m³) of each room.
3.
Calculate the refrigerant concentration C (kg/m³) of the
room according to the following equation:
R
— = C
V
R: Total Quantity of Charged Refrigerant (kg)
V: Room Volume (m³)
C: Refrigerant Concentration (
0.3 kg/m³)
n
Countermeasure for Refrigerant Leakage According
to KHK Standard
The facility shall be arranged as follows referring to the
KHK standards, so that the refrigerant concentration will be
bellow 0.3 kg/m³.
1.
Provide a shutterless opening which will allow fresh air
to circulate into the room.
2.
Provide a doorless opening of 0.15% or more size to
the floor area.
3.
Provide a Ventilator, Linked with a gas leak detector,
of 0.4 m³/min or more ventilating capacity per
Japanese Refrigeration Ton (=compressor
displacement m³/h/8.5(R22) or 9.8(R407)) of the air
conditioning system utilizing refrigerant R-22.
RAS-5FSG
2.15 ton
RAS-5FS3
2.48 ton
RAS-8FSG
3.74 ton
RAS-8FS3
4.31 ton
RAS-10FSG
4.01 ton
RAS-10FS3
4.63 ton
RAS-16FSG
5.78 ton
RAS-16FS3
6.66 ton
RAS-20FSG
7.36 ton
RAS-20FS3
8.49 ton
4.
Pay a special attention to the place, such as a
basement, etc., where refrigerant can stay, since
refrigerant is heavier than air.
1/25 ~ 1/100 Down-Slope
Common Drain Piping
(Horizontal)
Connecting Pipe Shall
be Downward
Common Drain Piping
(Vertical)
>
100m
m
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...