1
44
TROUBLESHOOTING
Alarm Code
29
Abnormality of Low Pressure Sensor for Outdoor Unit
n
”RUN” light flickers and ”ALARM” is indicated on the remote control switch.
n
The unit No., alarm code and the unit code is alternately indicated on the set temperature section, and the
unit No. and alarm code are indicated on the display of the outdoor unit PCB.
This alarm code is indicated when the pressure sensor voltage decreases lower than 0.1 V or increases
higher than 4.9V during running.
Is the connection CN8 of
the outdoor unit PCB1
mated loose?
Yes
Connect correctly.
No
Is 5 VDC applied across #1
and #3 of the connector
CN8 of the outdoor circuit
board PCB1?
No
Faulty PCB1
Yes
Is voltage under 0.1 VDC
or over 4.9 VDC across #2
and #3 of the connector
CN8 of the outdoor unit
PCB1?
No
Faulty PCB1
Yes
Yes
Is the Check Joint clogged?
Replace check joint.
No
Abnormality with low
Pressure Sensor.
Phenomenon
Cause
Check Item
Action
(Turn OFF main switch)
Fault
Check output voltage is
correct.
Replace pressure sensor if
faulty.
Faulty High
Pressure
Sensor
Incorrect Connection
Check connections.
Repair wiring and
connections.
Faulty PCB
Replace PCB and check
operation.
Replace PCB if faulty.
Indicated
Pressure Value is
Excessively High
or Low
Malfunction of Pressure
Sensor due to Faulty Check
Joint
Check for clogging of
check joint.
Replace check joint.
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...