1
24
TROUBLESHOOTING
Is DSW10-1P
(Terminal Resistance)
on PCB1 ON?
No
Set it correctly.
Yes
Is LED1 (red) on
PCB1 ON?
No
Is the voltage between
faston terminal "R1"
and "N" of PCB1 220V
or 240V?
No
Check the fuses of
outdoor unit power
supply.
Yes
Yes
Remove CN2 of
PCB1. *1)
Is connector (PCN1,
CN1) for transformer
loosened?
Yes
Plug PCN1 and CN1
correctly
Yes
Yes
Is LED3 (yellow) on
PCB1 ON?
Yes
Is the fuse for PCB1
melted?
Yes
Replace fuse.
No
No
Is LED3 (yellow) on
PCB1 flickering more
than once in 10
seconds?
No
Faulty PCB1
Yes
Connect CN2 of PCB1.
PCB1: Outdoor Unit Printed Circuit Board
PCB1’: Indoor Unit Printed Circuit Board
Yes
Is LED3 on PCB1' ON?
Yes
Is LED3 (yellow)ON
even if CN2 of PCB1’ is
removed?
Yes
Faulty PCB1.
No
No
Check other Indoor
Units
Is LED3 (yellow) on
PCB1’ flickering more
than once in 10
seconds?
No
Check wiring between
outdoor unit and
indoor units or fuse
(EF1) for PCB1.
Yes
Does refrigeration
system setting between
DSW1 on PCB1’ and
DSW5 on PCB1’
correspond?
No
Set correctly.
Yes
Does Alarm occur with
all indoor units?
No
Faulty PCB1'.
Yes
Faulty PCB1.
Indoor
Unit
Outdoor
Unit
Summary of Contents for FS3 Series
Page 2: ......
Page 4: ......
Page 114: ......
Page 190: ......
Page 192: ...3 20 MAIN PARTS n Control board 1 PCB1 2 2 ...
Page 193: ...3 MAIN PARTS 21 n Fan Control Board PCB2 ...
Page 194: ...3 22 MAIN PARTS n Inverter Board PCB3 n Snubber Board PCB5 ...
Page 196: ...3 24 MAIN PARTS n Control Board PCB of Indoor Unit Only for RPK Model ...
Page 198: ...3 26 MAIN PARTS n PC 5H ...
Page 199: ...3 MAIN PARTS 27 3 11 CIRCUIT DIAGRAM FOR PRINTED CIRCUIT BOARD OF RECEIVER ...
Page 200: ......
Page 239: ......
Page 240: ...SMGB0001 06 01 Printed in Spain ...