HDG Bavaria GmbH 07/2008
HDG M299/300/350/400 - Version 1 - en
6 Using the heating system – TIME menu
99
S
ETTING
TIMES
FOR
THE
HEAT
EXCHANGER
ASH
REMOVAL
AUGERS
AND
THE
CLEANING
SYSTEM
This submenu is used for setting times for the heat exchanger ash
removal augers and the time for the movements of the cleaning
system.
✎
See “Procedure” in this section.
S
ETTING
MAIN
CLEANING
In this submenu you can set up to two times for the main cleaning
Cleaning and ash removal are activated at the preset time.
✎
See “Procedure” in this section.
Time
3-05
Ash auger. exch Runtime
:
60 /
0 s
Ash auger. exch Pause time
:
60.0 / 0.0 m
Cleaning system pause time
:
12.0 / 0.0 h
Cleaning system runtime
:
140 /
0 s
END
When changing the heating material, the burn-out behaviour of the
boiler must be checked in the area of the heat exchanger surfaces.
If necessary, adjust the
Cleaning pause time
parameter. In
general, only this parameter should be changed and the
Cleaning system runtime
parameter only changed in
exceptional instances.
Cleaning
3-06
On: 00:00
On: 00:00
Time 11:50
END