6 Using the heating system – SERVICE menu
124
HDG M299/300/350/400 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
A
DAPTING
THE
FUEL
QUANTITY
/O2
This menu allows fuel to be increased or adapted within a range
defined by the Delta Min/Max values.
✎
See “Procedure” in this section.
S
ETTING
VACUUM
PRESSURE
CONTROL
VALUES
This menu is used to define the settings for fan speed with the HDG
cyclone dust extractor and the vacuum pressure value for the
vacuum pressure control.
✎
See “Procedure” in this section.
S1_Partial load: 12 %
S2_Partial load: 0 %
S1_Level 1
: 50 %
S2_Level 1
: 100 %
S1_Level 2
:100 %
S2_Level 2
: 100 %
S1_Full load : 100 %
S2_Full load
: 100 %
END
The fuel quantity/O2 settings apply for
Combustion control
as
well as
Combustion and output control
.
✎
See section “6.6 ON/OFF menu”, under “Setting the control,
boiler activation and Lambda Stop”.
Fuel quant modification by O2 R-3
6-09
Delta_FUE_MIN: -10%
FUEL_SET:
50.0%
Delta_FUE_MAX: 10%
Fuel_ACT:
50.0%
Delta_FUE_ACT: 0%
Delay
: 10s
END
The standard setting is -10% for
Delta FUE_MIN
and 10% for
Delta FUE_MAX
.
PID pressure control fan
6-10
MAX : 100%
P_Min
:
-15pa
KP: 65.0
MIN :
15%
P_Max
:
-25pa
TN:
11.0
ACT : 15%
P_Set:
-15pa
TV:
0.0
Fact.: 5% P_Act :
-30pa
KP_:
97.5
END
The standard setting is 100% for
MAX
and 15 % for
MIN
.
Summary of Contents for M299
Page 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Page 2: ......
Page 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 173: ...173 NOTICE ...
Page 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 175: ......