6 Using the heating system – SERVICE menu
116
HDG M299/300/350/400 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
•
Combustion chamber set temperature 30/100%
The combustion set temperature for the chimney sweep test in
partial load (30%) and nominal load (100%) can be set.
✎
See “Procedure” in this section.
P
EAK
LOAD
BOILER
MONITORING
An additional peak load boiler can be integrated using a
third accumulator temperature sensor.
The actual (ACT) temperature on the accumulator middle sensor
must be below the SET temperature
If the set value for the temperature increase is not reached within the
specified delay time, the peak load boiler is automatically activated.
✎
See “Procedure” in this section.
F
LUE
GAS
TEMPERATURE
•
Cleaning system start
When this set temperature is exceeded, the cleaning system starts
up.
•
Max. flue gas temperature
Chimney sweep mode
5-12
Enable boiler temperature :
70 / 60 °C
Enable comb. chamb. temp.
:
550 / 328 °C
Boiler temp. Set 30/100%
:
85 / 85 °C
Comb.chamb.set temp. 30/100% : 500 / 570 °C
END
This is an optional submenu and only available with double heating
systems (if necessary, also with oil/gas boilers).
Peak load boiler
5-13
Control accumulator temperature top
Temp. rise less than
5 / 70°C
Delay time
30 / 0 m
END
Summary of Contents for M299
Page 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Page 2: ......
Page 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 173: ...173 NOTICE ...
Page 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 175: ......