6 Using the heating system – Maintenance function
126
HDG M299/300/350/400 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
6.12 Maintenance function
The maintenance function is used to interrupt the current operating
mode and activate the burning out phase. When the burn-out time
has elapsed, maintenance is enabled and the primary and secondary
air fans switch off. Only the flue gas fan continues running with
controlled vacuum pressure. This serves to suction up dust and
remove radiant heat during cleaning and maintenance work.
After the cleaning and maintenance work is completed, the function
must be deactivated. The boiler switches back to the previous mode.
1.
Press the
F5
key under the standard display screen.
✓
You are in the
Service
menu.
✓
The display changes to the
Service 5-01
submenu.
2.
Press the
F3
key under the
Maintenance
command.
✓
The display changes to the
Function 1-10
submenu.
3.
Press the
F4
key under the
On
command.
✓
The message
Waiting for enabling
appears in the display.
✓
The boiler switches to the
burning out phase
.
✓
When the burn-out time is complete, the message
Maintenance enabled
appears in the display.
Service
5-01
Digital inputs 0-15
00000000 00000000
Digital outputs 0-15
00000001 00000000
Mainte
n.
END
Function
1-10
Maintenance
: On
Waiting for enabling
On
Off
END
Function
1-10
Summary of Contents for M299
Page 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Page 2: ......
Page 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 173: ...173 NOTICE ...
Page 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 175: ......