HDG M299/300/350/400 - Version 1 - en
8 Troubleshooting – Possible faults
163
WA197
Accumulator
lower
temperature
sensor faulty
•
Accumulator sensor faulty
•
Line faulty
•
Analogue module faulty
•
Check accumulator sensor
•
Check the electrical
connection
•
Replace analogue module
WA198
Combustion unit
temperature
faulty
•
Combustion chamber
temperature sensor is faulty
•
Line faulty
•
Analogue module faulty
•
Check combustion chamber
temperature sensor
•
Check the electrical
connection
•
Replace analogue module
WA199
Heat exchanger
cleaning drives
defective
•
Motor is faulty
•
Check the motor
WA200
Check ash auger
heat exchanger
•
Ash augers runtime
monitoring faulty
•
Ash auger blocked
•
Motor is faulty
•
Drive chain torn
•
Check limit switch (orange
LED lights up with contact)
•
Check ash auger
•
Check the motor
•
Check drive chain
WA202
Combustion
chamber
temperature
sensor 2 faulty
•
Combustion chamber
temperature sensor is faulty
•
Line faulty
•
Analogue module faulty
•
Check combustion chamber
temperature sensor
•
Check the electrical
connection
•
Replace analogue module
WA203
Flue gas sensor
faulty
•
Flue gas temperature sensor
faulty
•
Line from flue gas
temperature sensor faulty
•
Check the flue gas
temperature sensor/line and
replace if necessary
WA205
Accumulator top
middle
temperature
sensor faulty
•
Accumulator sensor faulty
•
Line faulty
•
Analogue module faulty
•
Check accumulator sensor
•
Check the electrical
connection
•
Replace analogue module
WA206
Accumulator
lower middle
temperature
sensor faulty
•
Accumulator sensor faulty
•
Line faulty
•
Analogue module faulty
•
Check accumulator sensor
•
Check the electrical
connection
•
Replace analogue module
WA208
Replace buffer
battery
•
Memory battery of control
unit discharged
•
Replace memory battery
WA209
Cleaning system
faulty
•
Motor incorrectly connected
•
Motor overload
•
Motor is faulty
•
Motor cable faulty
•
Faulty limit switch
•
Check the motor connection
•
Check the drive
•
Check the motor
•
Check the motor cable
•
Check limit switch
No.
Fault
Cause
Remedy
Table 8/1 - Faults (continuation)
Summary of Contents for M299
Page 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Page 2: ......
Page 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 173: ...173 NOTICE ...
Page 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 175: ......