HDG Bavaria GmbH 07/2008
HDG M299/300/350/400 - Version 1 - en
6 Using the heating system – SERVICE menu
109
S
ERVICE
MESSAGES
1 -
SETTING
REMINDER
TIME
This submenu can be used to set various times at which service
messages should appear.
•
Cleaning WA grate
When the preset operating hours are exceeded, the warning
“
Please clean the primary air space of the
stepped grate
" appears. The heating system does not shut off at
the appearance of this warning. The “0” setting deactivates this
function.
•
Cleaning ST grate
When the preset operating hours are exceeded, the fault message
“
Please clean the primary air space of the
stepped grate
" appears. The heating system shuts off at this
fault. The “0” setting deactivates this function.
•
WA Lubricate stoker auger
When the preset runtime of the stoker auger is exceeded, the
warning “
Please lubricate the screw stoker bearing
”
appears. The heating system does not shut off at the appearance of
this warning. The “0” setting deactivates this function.
1.
Open the
Service 5-02
submenu.
✎
See “Procedure” in this section.
2.
Using the
F1
key select
service messages 11-03
in the
submenu.
3.
Press the
F5
key under the
RESET
command to reset the times.
S
ERVICE
MESSAGES
2 -
SETTING
REMINDER
TIME
•
WA Empty ash box
When the preset runtime of the ash removal auger is exceeded, the
warning “
Please empty ash box
” appears. The heating system
does not shut off at the appearance of this warning. The “0” setting
deactivates this function.
Service messages
11-03
Clean WA grate
:
400.0/
0.0 h
Clean ST grate
:
450.0/
0.0 h
WA Lubricate sto.auger:
150.0/
0 h
RESET
END
Summary of Contents for M299
Page 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Page 2: ......
Page 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 173: ...173 NOTICE ...
Page 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 175: ......