6 Using the heating system – SERVICE menu
122
HDG M299/300/350/400 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
S
ETTING
PRESET
VALUES
FOR
PRIMARY
AIR
FLAPS
In this menu, you can set the preset values for the primary air flaps for
controlled operation of the boiler.
✎
See “Procedure” in this section.
E
NTERING
THE
RESIDUAL
OXYGEN
SETTING
This menu is used to enter the residual oxygen setting for controlled
operation of the boiler.
✎
See “Procedure” in this section.
END
The difference between primary air quantity
Air_Max
and
Air_Min
should be specified as a range adapting to the required
value (approx. 25 %).
The primary air settings apply for
Combustion control
as well
as
Combustion and output control
.
✎
See section “6.6 ON/OFF menu”, under “Setting the control,
boiler activation and Lambda Stop”.
Preset value primary air flaps
6-05
P1_Partial load: 40 % P2_Partial load: 0 %
P1_Level 1:
100 % P2_Level 1
: 20 %
P1_Level 2: 100 % P2_Level 2
: 35 %
P1_Full load :
100 % P2_Full load
: 50 %
END
The residual oxygen setting applies for
Combustion control
as
well as
Combustion and output control
.
✎
See section “6.6 ON/OFF menu”, under “Setting the control,
boiler activation and Lambda Stop”.
O2 preset value
R-2
6-06
O2_MAX :
7.0 %
CCT_SOLL: 650°C
O2_MIN :
7.0 %
CCT_IST : 50°C
O2_SET :
7.0 %
O2_ACT : 12.8
END
Summary of Contents for M299
Page 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Page 2: ......
Page 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 173: ...173 NOTICE ...
Page 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 175: ......