6 Using the heating system – Performing the chimney sweep test
129
✎
See chapter “7 Cleaning and servicing the heating system”,
section “7.1 Cleaning and maintenance schedule”.
2.
Check that the lambda sensor is securely mounted and tighten it
if necessary.
✎
See chapter “7 Cleaning and servicing the heating system”,
section “7.1 Cleaning and maintenance schedule”.
D
URING
THE
TEST
Please observe the following when carrying out the chimney sweep
test:
•
Make sure that there is sufficient fuel in the fuel storage to avoid
interruption of material feeding during the measurement.
•
No fault should be present in the system.
1.
Press the
F5
key under the standard display screen.
✓
You are in the
Service
menu.
✓
The display changes to the
Service 5-01
submenu.
.
Warning!
Material damage and injury due to incorrect chimney sweep test
The chimney sweep test requires comprehensive technical
knowledge.
Only permit authorised specialists to perform the chimney sweep
test.
At the start of the measurement, the boiler temperature should not
exceed 75°C. If there is an accumulator, its temperature should not
exceed 60°C. Ensure there that the heating circuit has sufficient
heat transfer capacity.
The chimney sweep measurement must be performed when
operating at full load. (It is absolutely essential to avoid the heating
up and burning out phases.) Having the test repeated by the
combustion engineer or by HDG specialists will incur charges.
Service
5.0
Digital inputs 0-15
00000000 00000000
Digital outputs 0-15
00000001 00000000
Main-
tenanc
e
END
Summary of Contents for M299
Page 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Page 2: ......
Page 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 173: ...173 NOTICE ...
Page 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 175: ......