6 Using the heating system – SERVICE menu
112
HDG M299/300/350/400 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
S
ETTING
REVERSE
FEEDING
AND
IGNITION
TEMPERATURE
•
Delay reverse movement
This submenu is used to change the delay in the reversal of the
feeding system. The feeding system reverses for overcurrent if the
rotary feeder becomes blocked. The change of rotational direction is
then delayed by this amount of time.
•
Reverse moving runtime
The running time of the backward running of the feeding system can
also be corrected. This value is limited to a maximum of three
seconds.
•
Reverse moving attempts
Setting the maximum number of reverse moving attempts.
•
Ignition temperature
If the temperature in the hot combustion chamber exceeds this
value, the HDG Control does not switch on the ignition fan for
starting the heating system.
✎
See “Procedure” in this section.
M
ODIFYING
THE
DOSAGE
PAUSE
MIN
.
OR
IMPULSE
MIN
.
AND
FEEDING
UNITS
LAG
TIME
OR
LEAD
TIME
PARAMETERS
•
Dosage pause min. and dosage impulse min.
– These parameters are used to set the minimum pause intervals
and running time of the extraction for the fuel metering.
Boiler temp. Overheating :
5 °C
Boiler temp. hysteresis :
2 °C
Return temperature minimum:
60 °C
Comb.chamb. temp. stop :
750 °C
END
Service
5-04
Reversing delay :
00.7 s
Reverse moving runtime :
01.0 s
Reverse moving attempts
:
3 x
Ignition temperature
:
200 °C
END
Summary of Contents for M299
Page 1: ...hdg bavaria com HDG M299 300 350 400 Operation Manual ...
Page 2: ......
Page 172: ...172 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 173: ...173 NOTICE ...
Page 174: ...174 HDG M299 300 350 400 Version 1 de HDG Bavaria GmbH Juli 2005 NOTICE ...
Page 175: ......