Example
An air return (Ø 25 mm) of 22 m is connected to a TITANUS PRO·SENS®
with a fan voltage of 6.9 V. The permissible overall pipe length for the pipe
system is 120 m. The following results for the maximum aspiration pipe
length:
5.3.9 Energy supply
When configuring the external energy supply, the alarm-ready state and the
alarm state of the connected units are taken into account. The state with the
higher current consumption is decisive for selecting the energy supply.
Refer to the chapter "Technical data" for the current consumption values of
the TITANUS PRO·SENS®.
Alarm state
Alarm current
In the event of an alarm, the energy supply must supply the alarm current
for:
▪ Connected devices
▪ Any connected accessories.
Alarm current [A]
Number of devices
Alarm current of devices [A]
Number of accessories 2
Alarm current/current consumption of accessories 2 [A]
Number of accessories x
Alarm current/current consumption of accessories x [A]
Max. aspiration pipe length = 120 m
– (22 m * 0.8) = 102.4 m
No standard conformity in case of wrong energy supply
The energy supply of the TITANUS PRO·SENS® must be approved in
accordance with AS ISO 7240
‑
4.
NOTICE