Diameter of aspiration apertures
Trigger thresholds
- not possible
O not feasible
Example
If blockage of 3 aspiration apertures of a total of 7 aspiration apertures is
intended to be detected, the airflow monitoring setting switch is to be set to
level III.
Number of aspiration apertures
2
3
4
5
6
7
8
9
10
Item
Punching diameter of the aspiration reducing film sheet [mm]
A
6.0
5.0
4.2
3.8
3.2
3.0
2.5
2.5
2.0
B
6.8
5.2
4.4
3.8
3.2
3.0
2.5
2.5
2.0
C
-
5.2
4.6
4.0
3.6
3.0
3.0
2.5
2.5
D
-
-
4.6
4.0
3.6
3.4
3.0
3.0
2.5
E
-
-
-
4.4
4.0
3.4
3.4
3.0
3.0
F
-
-
-
-
4.0
3.8
3.4
3.4
3.0
G
-
-
-
-
-
3.8-
3.8
3.4
3.4
H
-
-
-
-
-
-
3.8-
3.8
3.4
I
-
-
-
-
-
3.8
3.6
J
-
-
-
-
-
-
-
-
3.6
Number of aspiration
apertures
2
3
4
5
6
7
8
9
10
1 blocked aspiration
apertures…
III
III
II
I
I
-
-
-
-
2 blocked aspiration
apertures…
O
O
III
III
II
I
I
-
-
3 blocked aspiration
apertures…
O
O
O
O
III
III
II
I
I
4 blocked aspiration
apertures…
O
O
O
O
O
O
III
II
I
5 blocked aspiration
apertures…
O
O
O
O
O
O
O
O
II
… identified when setting level x.
For project planning in compliance with AS ISO 7240-20, level I or II airflow
monitoring must be set.
NOTICE
Summary of Contents for Ampac TITANUS PRO-SENS
Page 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Page 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Page 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Page 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...