MAN3184 - TITANUS PRO
•
SENS®
49
Figure 33:
Example of a symmetrical and an asymmetrical U-pipe system
The previous figure shows an example of a U-pipe system with symmetrical
or asymmetrical structure and with the diameters of the aspiration apertures
calculated according to the chapter "Standard planning". The diameters of
the aspiration apertures are determined for each pipeline branch individually
and depend on the number of aspiration apertures on the pipeline branch in
question. The corresponding opening diameters can be found in the tables in
the chapter "Opening diameter".
Pipe connections
The TITANUS PRO·SENS® has two pipe connections. One pipe system
may be connected to each of these pipe connections, as long as two
detector modules are being used.
This means that only one aspiration pipe can be connected if only one
detector module is used.
Longer pipe supply lines
Pipes with Ø 32 mm or Ø 40 mm can be used for long pipe supply lines in
accordance with the chapter "Special project planning".
This reduces the air resistance of the pipe supply line or makes it possible to
achieve a greater equilibrium for aspiration via outgoing stubs (e.g. high-bay
warehouses).
Branch length
In order to ensure a short transport time for the smoke aerosols in the
aspiration pipe and thus enable rapid detection, it is better to plan several
shorter branches than a few long ones (preferably a U- or double U-pipe
system).
Summary of Contents for Ampac TITANUS PRO-SENS
Page 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Page 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Page 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Page 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...