5.3.2.3 M-pipe system
Figure 48:
M-pipe system for simplified pipe project planning
Threshold values
Min. distance between the device and the T-piece
2 m
Max. distance between the device and the T-piece
20 m
Max. branch lengths
20 m
Max. overall pipe length Ø 25 mm
80 m
Min. distance between two aspiration apertures (d)
0.1 m
Max. distance between two aspiration apertures (d)
4 m
Max. number of aspiration apertures per pipe system
18 units
Diameter of aspiration apertures
Number of aspiration apertures
3
6
9
12
15
18
Punching diameter of the aspiration reducing film sheet [mm]
5.0
3.6
3.0
3.0
2.5
2.5