MAN3184 - TITANUS PRO
•
SENS®
72
Diameter of aspiration apertures
Trigger thresholds
- not possible
O not feasible
Example
If blockage of 3 aspiration apertures of a total of 9 aspiration apertures is
intended to be detected, the airflow monitoring setting switch is to be set to
level I.
Number of aspiration apertures
3
6
9
12
Item
Punching diameter of the aspiration reducing film sheet [mm]
A
4.4
3.4
3.0
2.5
B
-
3.6
3.0
2.5
C
-
-
3.2
3.2
D
-
-
-
3.2
Number of aspiration
apertures
3
6
9
12
1 blocked aspiration
aperture…
III
I
-
-
2 blocked aspiration
aperture…
O
II
-
-
3 blocked aspiration
aperture…
O
III
I
-
4 blocked aspiration
aperture…
O
O
II
I
5 blocked aspiration
aperture…
O
O
O
II
6 blocked aspiration
aperture…
O
O
O
III
7 blocked aspiration
aperture…
O
O
O
O
… identified when setting level x.
For project planning in compliance with AS ISO 7240-20, level I or II airflow
monitoring must be set.
NOTICE