Drill hole intervals
The distances of the aspiration apertures to each other and to the wall of the
duct are listed in the following table.
Duct cross-section
≤ 0.5 m²
Duct cross-section
> 0.5 m²
Distance of aspiration apertures from the wall
100 to 200 mm
200 to 300 mm
Mutual distance between aspiration apertures
100 mm
150 mm
Aspiration aperture
diameter
The diameters of the aspiration apertures are obtained from the number of
aspiration apertures. The precise value can be found in the chapter "Project
planning"
➔
"Simplified pipe project planning".
The pipe connection is achieved with an end cap without drilling.
Arrangement
The aspiration apertures must be arranged against the airflow.
Note for the project planning that the air conditioning ducts for the installation
of the pipe system are often only accessible from two sides.
Example
The following illustration shows two project planning examples of pipe
systems in air conditioning ducts.