7.4.2 Other ceiling ducts
Figure 86:
Capillary hose and upstream panel installation
The following work steps are required to install a ceiling duct:
► Rid the bonding surfaces of dirt and grease with the stipulated cleaning
agent before gluing.
► Adhere the necessary aspiration reducing film sheet in the pipe hood
(according to project planning guidelines).
► Glue the hose connection with the respective pipe hood to the aspiration
pipe using Tangit glue.
► Drill a Ø 12 mm hole in the suspended ceiling for each ceiling duct.
► Determine the required length for the aspiration hose and cut it to size.
Insert the cut hose through the suspended ceiling and attach it to the
hose connection on the pipe hood of the aspiration pipe. Heat the hose
with a hot air blower if necessary.
► Glue the capillary hose into the drill hole of the suspended ceiling using
Tangit glue.