The table shows the selectable sensitivity levels of the
TITANUS PRO·SENS®
Response sensitivity (main alarm) TITANUS PRO·SENS®
Detector module
Type DM
‑
TT
‑
50
‑
L
[% light obscuration/m]
Detector module
Type DM
‑
TT
‑
10
‑
L
[% light obscuration/m]
Detector module
Type DM
‑
TT
‑
01
‑
L
[% light obscuration/m]
-
0.8
0.12
-
0.4 (standard)
0.06 (standard)
1
0.2
0.03
0.5 (standard)
0.1
0.015
Project planning of the monitoring area always takes place according to the
national provisions for point smoke detectors.