► Spread the two retaining clips apart again and insert the new detector
module. Both clips must be positioned against the detector module and
audibly engage. Then press both retaining clips together again.
► Reconnect the detector module to the basic board using the ribbon
cable.
Connection: X1 (HEAD1) or X3 (HEAD2)
► Reconnect the display circuit board to the basic board.
Connection: X4 (DISPLAY)
► Check the pipe system for tightness and blockage before initialising the
pipe system.
► Reconnect the operating voltage.
► Press the flow init button S2 on the detector module to initialise the pipe
system.
► Close the housing cover.
The device must have been in operation for at least 30 min before the
TITANUS PRO·SENS® can be correctly calibrated to the connected pipe
system.