MAN3184 - TITANUS PRO
•
SENS®
70
Diameter of aspiration apertures
Trigger thresholds
- not possible
O not feasible
Example
If blockage of 3 aspiration apertures of a total of 10 aspiration apertures is
intended to be detected, the airflow monitoring setting switch is to be set to
level I.
Number of aspiration apertures
2
4
6
8
10
12
14
Item
Punching diameter of the aspiration reducing film sheet [mm]
A
5.2
3.6
3.4
3.2
2.5
2.5
2.0
B
-
4.0
3.4
3.2
3.0
2.5
2.0
C
-
-
3.6
3.4
3.0
2.5
2.5
D
-
-
-
3.4
3.2
3.0
2.5
E
-
-
-
-
3.2
3.0
3.0
F
-
-
-
-
-
3.2
3.0
G
-
-
-
-
-
-
3.2
Number of aspiration
apertures
2
4
6
8
10
12
14
1 blocked aspiration
aperture…
III
II
I
-
-
-
-
2 blocked aspiration
aperture…
O
III
II
I
-
-
-
3 blocked aspiration
aperture…
O
O
III
II
I
-
-
4 blocked aspiration
aperture…
O
O
O
III
II
I
-
5 blocked aspiration
aperture…
O
O
O
O
III
II
I
6 blocked aspiration
aperture…
O
O
O
O
O
III
II
7 blocked aspiration
aperture…
O
O
O
O
O
O
III
… identified when setting level x.
For project planning in compliance with AS ISO 7240-20, level I or II airflow
monitoring must be set.
NOTICE
Summary of Contents for Ampac TITANUS PRO-SENS
Page 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Page 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Page 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Page 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...