MAN3184 - TITANUS PRO
•
SENS®
129
7.1.1 Installing the pipe system
The pipe system must be installed according to project specifications and
taking into account the project planning guidelines (see chapter "Project
planning").
► Cut the pipes with a pipe cutter or a metal saw. Deburr the cut edges
and remove any shavings.
► Rid the bonding surfaces of dirt and grease with the stipulated cleaning
agent before gluing. Then, glue the pipe joints so they are airtight with
the fittings.
Aspiration pipe
halogen-free
Aspiration pipe
(UPVC)
Cleaner
Adhesive
Pipe cutter
ABSR-2518
R-2519
Tangit cleaner
Tangit glue
Pipe shears or
ABSR-3220
R-3218
cutter (38 mm)
ABSR-4025
R-4019
► Minimise the pipe lengths and changes of direction. Angles have
extremely high flow resistance. Therefore, they are only to be used
where they cannot be avoided due to structural constraints. If necessary,
the pipe length must be reduced in relation to the angles used (an angle
corresponds to a straight pipe length of 1.5 m).
► Mount the pipe system firmly so that it will neither bend nor become
distorted. Fasten the pipe with pipe clips without rubber inserts. The
intervals between the pipe clips should not exceed 80 cm. In case of
high temperature fluctuations, reduce the intervals between the pipe
clips to maximum 30 cm.
Adhesives and cleaning products contain solvents and are flammable. The
safety notes of the supplier must be observed prior to use.
ATTENTION
Elbows are to be given absolute priority over angles. Too many angles and
elbows reduce the air speed in the aspiration pipe and thus increase the
detection period.
NOTICE
Summary of Contents for Ampac TITANUS PRO-SENS
Page 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Page 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Page 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Page 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...