6.4.1.11 Connection of the fan on TITANUS PRO·SENS®
‑
SL
The electrical connection of the fan control circuit board is made using
terminal strip X5 (FAN) on the TITANUS PRO·SENS® basic board.
The electrical connection of the fan is made using terminal strip X1 (FAN) on
the fan control circuit board.
▪ Connect terminal 1 of terminal strip X5 on the basic board to terminal 2
(+) of terminal strip X2 on the fan control circuit board.
▪ Connect terminal 2 of terminal strip X5 on the basic board to terminal 1
(-) of terminal strip X2 on the fan control circuit board.
▪ Connect the brown fan connection cable to terminal strip X1 / terminal 1
of the fan control circuit board.
▪ Connect the yellow fan connection cable to terminal strip X1 / terminal 2
of the fan control circuit board.
▪ Connect the purple fan connection cable to terminal strip X1 / terminal 3
of the fan control circuit board.
6.5 Installing the reset circuit board
The reset circuit board can be optionally used in the TITANUS PRO·SENS®.
The installation of reset circuit board in the housing is carried out using a
mounting plate (see installation kit for additional modules type KT
‑
HS
‑
1). If
several TITANUS PRO·SENS® are connected to a detector line, the reset
circuit board is only installed in the last TITANUS PRO·SENS® of the
detector line. The electrical connection of the reset circuit board is made
according to the circuit diagram in the chapter "Electrical connection".
When changing the fan voltage, perform airflow initialisation again. Only
close or open bridge BR1 and BR2 when the device is switched off.
ATTENTION
Upon delivery of the TITANUS PRO·SENS®, the fan was connected in the
factory.
NOTICE
Summary of Contents for Ampac TITANUS PRO-SENS
Page 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Page 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Page 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Page 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...