INTRODUCTION
Heatit Z-Smoke Detector is a wireless smoke sensor with built-in
PIR motion sensor, temperature sensor and emergency light.
INSTALLATION
Installation must be done by a qualified electrician in accordance
with the National Building Codes. Before installation, disconnect
any power to the smoke detector. During installation of the smoke
detector, power to the smoke detector must be disconnected AT
ALL TIMES!
•
Screw the mounting bracket onto the wall/ceiling. If used with
cable trunkings mount the adapter with the bracket mounted
on the bottom.
•
Unscrew the connection cover.
•
Connect the ”L” phase to one of the Wago connectors on the
back of the smoke detector and connect the ”N” phase to the
other Wago connector.
•
Switch on the switch. Illustrated below.
•
Align the four notches on the smoke detector with the hooks
on the mounting bracket. Rotate clockwise to lock the hook.
a.
LED-indicator/function button/emergency light
b. IR-lens
c.
Buzzer
d. Connection compartment fixing screw
e.
Connection compartment
f.
Hooks
g. Mounting bracket
h. Mounting holes (for the hooks on the mounting bracket)
i.
Cable channel adapter
j.
Mount by aligning notches and hooks
ADD/REMOVE
After power is applied, the smoke detector initiates a 1-minute
warm-up period. During this minute, the device will automatically
enter add/remove mode, and may now be added to the system
via the primary controller/gateway.
Please refer to your primary controller/gateway manual on how to
enter add/remove mode.
SERIAL CONNECTION
1. Add all smoke detectors to the same network.
2. Assign the smoke detectors to the correct zone/room in
primary controller.
3. Access associations from the primary gateway (please refer to
primary controller manual).
4. Assign associations from each device using association
group 2 (Sensor Basic Set) to all other smoke detectors.
Heatit Controls AB can not be held liable for typographical errors, other errors or
omittances in our information. Product specifications may change without further notice.
All electrical installations must be carried out by a licensed electrician. The product must
be installed in accordance with national building codes and our installers manual.
Protocol
Z-Wave
Chip
Z-Wave 500 chip
Battery
230V AC 50Hz
200mAh, NiMh back-up battery
Temp. sensitivity
±1°C
Alarm
85dB at 3 meters distance
Smoke sensor
Photoelectric
Ambient temp.
0°C to 50°C
Humidity
Max. 85% RH
Range, PIR
Up to 8m at 3m mounting height
IP Code
IP 20
Size (LxWxH)
105mm x 105mm x 41mm
(ex. adapter)
Approvals
Z-Wave Plus
CE, RoHS,
EN 14604:2005, 14604/AC:2008
TECHNICAL DATA
Heatit Controls AB l Läkarvägen 4, 454 31 BRASTAD, SWEDEN
Phone: +47 61 18 77 77 l [email protected] – www.heatit.com
Read the full manual at:
manuals.heatit.com
230V
a
b
c
g
h
d
e
f
Lock
j
i
Cable slots
dimensions 10x12mm
HEATIT Z-SMOKE
DETECTOR
Quick Guide
Ver 2020-A
230V