Figure 70:
Installing the reset circuit board in the TITANUS PRO·SENS®
Installation
The following work steps must be performed for installation of the reset
circuit board in the TITANUS PRO·SENS®:
► Carefully unlock the clips on the housing using a flat-head screwdriver
by simultaneously pressing in the closing flaps on one side. Then
carefully lift the housing cover.
► Pull the display circuit board cable from the connection circuit board and
remove the housing cover.
► Insert the calculated termination resistor (termination resistor is not
supplied, power ¼ W)
R
ER
into connection terminal X1.
► Fixing the reset circuit board to the mounting plate (installation kit for
additional module type KT-HS-1) with 2 plastic spacers (enclosed with
the reset circuit board).
► Fit the mounting plate equipped with the reset circuit board in the
TITANUS PRO·SENS® housing at the position marked in the figure.
► Perform electrical connection of the reset circuit board according to the
circuit diagram, see chapter "Electrical connection" (connection X2).
► Reconnect the display circuit board cable to the connection circuit board
and reattach the housing cover.
► Fasten the cover again by letting the clips click in.
Summary of Contents for Ampac TITANUS PRO-SENS
Page 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Page 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Page 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Page 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...