Patented, U.S. Patent No. Des. 428,351; 6,380,846; 6,632,108

Document 51479 

I56-2268-003

Description
The BG-12LPS pull station is a non-coded, dual-action manual pull station with a key-lock reset 

feature. It provides Fire•Lite control panels with two (2) normally open (N/O) alarm initiating 
input signals. “Pre-signal” input is activated by pushing in, then pulling down the dual action 
handle. A “General” alarm input signal can be manually activated via a momentary rocker switch 
mounted inside the unit. This general alarm switch can only be accessed by opening the cover 
with the supplied key/lock.

The  BG-12LPS  meets  the ADAAG  controls  and  operating  mechanisms  guidelines  (section 
4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate the pull station. 
Operating instructions are molded into the pull station handle along with Braille text. Molded 
Terminal numbers are also present.

Ratings 

Switch contacts (N/O) are gold plated for reliability and rated at 0.25 A at 30 volts (AC or 
DC).

Installation

The BG-12LPS pull station can be surface mounted to an SB-10 or SB-I/O surface backbox 
or semi-flush mounted on a standard double-gang or 4

 (10.16 cm) square electrical box. The 

optional BG-TR trim ring can be used if the BG-12LPS is to be semi-flush mounted.

Operation
To activate the dual-action pull station, push in and pull down on the handle. The word

‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull station 

is reset.

The pull station includes two independently operated Single Pole, Single Throw (SPST) Normally 
Open (N/O) Switches for pre-signal/ general alarm applications.

Resetting the Pull Station

1.  Insert the key into the lock and rotate 1/4 turn counterclockwise.
2.  Open the door until the handle returns to normal.
3.  Close and lock the door.

Note:

  Closing the door automatically resets the switch to the ‘Normal’ position. Opening the 

door will not activate or deactivate the pre-signal toggle switch.

STRIP GAUGE

1  2  3  4

To  Next  Pre-Signal  +

–  To  Next  Device  on
+  General  Alarm  IDC

–  From  FACP
+  General  Alarm  IDC

Device  on  IDC  –

From  FACP  +

Pre-Signal  IDC  –

P0229-00

Wiring

CAUTION! Do not detach the door of the pull station 

during installation. The door of the pull station cannot be 
reattached to the backplate after the backplate has already 
been installed onto an electrical box.

CAUTION!

I n s t a l l   t h e   F i r e • L i t e   B G - 1 2 L P S   p u l l   s t a

-

tion  in  accordance  with  these  instructions,  

applicable  NFPA  standards,  national  and  local  Fire 
and  Electrical  codes  and  the  requirements  of  the AHJ 
(Authority Having Jurisdiction). Regular testing of the 
devices  should  be  conducted  in  accordance  with  the 
appropriate  NFPA  standards.  Failure  to  follow  these 

directions  may  result  in  failure  of  the  device  to  report 

an  alarm  condition.  Fire•Lite  is  not  responsible  for 

 

devices  that  have  been  improperly  installed,  tested  or 

maintained.

ADA Compliance

For ADA compliance, if the clear floor space only allows 

forward  approach  to  an  object,  the  maximum  forward 
reach  height  allowed  is  48  inches  (121.92  cm).  If  the 
clear  floor  space  allows  parallel  approach  by  a  person 
in a wheelchair, the maximum side reach allowed is 54 
inches (137.16 cm).

BG-12LPS

Manual Pull Station

WARNING!  Do not loop wiring under any 

terminals. Break wire run to 
maintain IDC supervision.

NORMA

L

ACTIV

ATED

PUSH FOR

GENERAL

ALARM

Toggle

Switch

for

Pre-Signal

Momentary

Rocker

Switch

for General

Alarm

Notification

UL PRODUCT

IDENTIFICATION

LABEL

P0230-00

Document 51479 

I56-2268-003