background image

Model SC7010BV

INTRODUCTION

Thank you for choosing First Alert

®

for your Smoke and Carbon

Monoxide Alarm needs. You have purchased a state-of-the-art Smoke
& Carbon Monoxide Alarm designed to provide you with early warning
of a fire or Carbon Monoxide. Key features include:
Smoke & Carbon Monoxide Combination Alarm. 
One alarm protects
against two deadly household threats.
Exclusive Voice Warning with Location will tell you the preprogrammed
location of the initiating unit and danger detected. Programmable up to
11 locations (ex. "basement"). When alarms sounds, if programmed for
basement it will say "Warning, evacuate, smoke in basement".
Spread Spectrum Horn Tone. Lower and varying horn frequency
makes it easier for elderly with normal age related hearing loss to hear
horn. Sweeps through the 2200 – 3400 Hz range.
Smart Interconnect can be interconnected to BRK Smoke, CO, and
Heat Alarms. One interconnect wire carries both smoke and CO alarm
signals.
Optipath 360 Technology

TM

provides 360 degrees of direct access to

the smoke sensor.
Single Button Test/Silence eliminates confusion. Depending on what
mode the alarm is in, pushing the button provides different functions
such as testing the alarm, silencing the alarm, re-testing the alarm
when in silence and clearing the Latching features.
Two Silence Features. Temporarily silence low battery chirp for up to
eight hours before replacing low battery or silence an unwanted alarm
for several minutes.
Two Latching Features. Alarm Latch: Easily identifies initiating alarm
even after alarm condition has subsided. Low Battery Latch: Identifies
which unit is in low battery condition.
Perfect Mount System includes a gasketless base for easy installation
and a mounting bracket that keeps the alarm secure over a wide 
rotation range to allow for perfect alignment.
Dust Cover is included to keep the alarm clean during construction.
Easy Installation/Maintenance features include a large opening in 
the mounting bracket for easy access to wiring. A battery pull tab that
keeps the battery fresh until the home is occupied. A Side Load Battery
Drawer allows for easy battery replacement without removing the alarm
from the ceiling or wall.
End of Life Signal. Provides audible confirmation alarm needs to be
replaced.
Improved UV Resistance keeps the alarm from discoloring over time.

© 2010 BRK Brands, Inc.  All rights reserved.
Distributed by BRK Brands, Inc.
3901 Liberty Street Road, Aurora, IL 60504-8122
Consumer Affairs: (800) 323-9005   •   www.firstalert.com

1

SMOKE & CARBON

MONOXIDE ALARM

All First Alert

®

Smoke Alarms conform to regulatory requirements,

including UL217 and are designed to detect particles of combustion.
Smoke particles of varying number and size are produced in all
fires.

Ionization technology is generally more sensitive than photoelectric
technology at detecting small particles, which tend to be produced
in greater amounts by flaming fires, which consume combustible

materials rapidly and spread quickly. Sources of these fires may include
paper burning in a wastebasket, or a grease fire in the kitchen.

Photoelectric technology is generally more sensitive than ionization
technology at detecting large particles, which tend to be produced
in greater amounts by smoldering fires, which may smolder for

hours before bursting into flame. Sources of these fires may include 
cigarettes burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on each
level and in every bedroom of your home.

USER’S MANUAL

AC Powered Smoke & Carbon Monoxide Alarm

Features:

Voice with Programmable Location
Two Latching Features
Smart Interconnect
Optipath 360 Technology

TM

Two Silence Features
Alkaline Battery Backup

IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
This user’s manual contains important information about your Alarm’s
operation. If you are installing the Alarm for use by others, you must
leave this manual—or a copy of it—with the end user.

ELECTRICAL SHOCK HAZARD. Turn off the power to the area
where the Smoke Alarm is installed before removing it from the
mounting bracket. Failure to turn off the power first may result in
serious electrical shock, injury or death.

This unit will not alert hearing impaired residents. 
It is recommended that you install special units which use
devices like flashing strobe lights to alert hearing impaired
residents.

• Installation of this unit must conform to the electrical codes

in your area; Articles 210 and 300.3 (B) of NFPA 70 (NEC),
NFPA 72, NFPA 101; SBC (SBCCI); UBC (ICBO); NBC (BOCA);
OTFDC (CABO), and any other local or building codes that
may apply. Wiring and installation must be performed by a
licensed electrician. Failure to follow these guidelines may
result in injury or property damage.

This unit must be powered by a 24-hour, 120VAC pure sine
wave 60Hz circuit. Be sure the circuit cannot be turned 
off by a switch, dimmer, or ground fault circuit interrupter.
Failure to connect this unit to a 24-hour circuit may 
prevent it from providing constant protection.

This Alarm must have AC or battery power to operate.
If the AC power fails, battery back-up will allow the alarm
to sound for at least 4 minutes. If AC power fails and the
battery is weak, protection should last for at least 7 days.
If AC power fails and the battery is dead or missing, the
alarm cannot operate.

• Never disconnect the power from an AC powered unit to

stop an unwanted alarm. Doing so will disable the unit and
remove your protection. In the case of a true unwanted
alarm open a window or fan the smoke away from the unit.
The alarm will reset automatically when it returns to normal
operation. Never remove the batteries from a battery 
operated unit to stop an unwanted alarm (caused by cooking
smoke, etc.). Instead open a window or fan the smoke
away from the unit. The alarm will reset automatically.

Connect this unit ONLY to other compatible units. See
“How To Install This Smoke Alarm” for details. Do not 
connect it to any other type of alarm or auxiliary device.
Connecting anything else to this unit may damage it or
prevent it from operating properly.

This Smoke/CO Alarm has a battery drawer which resists
closing unless a battery is installed. This warns you the
unit will not operate under DC power without a battery.

• Do not stand too close to the unit when the alarm is 

sounding. It is loud to wake you in an emergency. Exposure
to the horn at close range may harm your hearing.

Do not paint over the unit. Paint may clog the openings to
the sensing chambers and prevent the unit from operating
properly.

The Mounting Bracket:
To remove the mounting bracket from the Alarm
base, hold the Alarm base firmly and twist the
mounting bracket counterclockwise. The mounting
bracket installs onto the junction box. It has a 
variety of screw slots to fit most boxes.

The Power Connector: 
The power connector plugs into a power input block 
on the Alarm. It supplies the unit with AC power.

• The black wire is “hot.”

• The white wire is neutral.

• The orange wire is used for interconnect.

If you need to remove the power connector, turn 
POWER OFF first.

Insert a flat screwdriver blade

between the power connector and the security tab
inside the power input block. Gently pry back the tab
and pull the connector free.

4

5

6

8

9

10

7

The Parts of This Unit

1

Mounting Bracket

2

Mounting Slots

3

Locking Pins (break out of
bracket)

4

Hot (Black) AC Wire

5

Neutral (White) AC Wire

6

Interconnect (Orange) Wire

7

Quick-Connect Power
Connector

8

Turn this way to remove
from bracket

9

Turn this way to attach to
bracket

10 Slide-Out Battery Drawer

HOW TO INSTALL THIS SMOKE/CO ALARM

THE PARTS OF THIS ALARM

This Smoke/CO Alarm is designed to be mounted on any standard wiring junction box up to a 4-inch (10 cm) size, on either the ceiling or wall (if allowed
by local codes). Read “Where to Install This Alarm” and “Where This Alarm Should Not Be Installed” before you begin installation. 
Tools you will need:  • Needle-nose pliers or utility knife • Standard flathead screwdriver  • Wire strippers.

Make sure the Alarm is not receiving excessively noisy power. Examples of noisy power could be major appliances on the same circuit, power
from a generator or solar power, light dimmer on the same circuit or mounted near fluorescent lighting. Excessively noisy power may cause
damage to your Alarm.

The basic installation of this Alarm is similar whether you want to
install one Alarm, or interconnect more than one Alarm. If you are
interconnecting more than one Alarm, you MUST read “Special
Requirements For Interconnected Alarms” below before you begin
installation.

ELECTRICAL SHOCK HAZARD. Turn off power to the area where
you will install this unit at the circuit breaker or fuse box before
beginning installation. Failure to turn off the power before installa-
tion may result in serious electrical shock, injury or death.

1. Remove the mounting bracket

from the base, and attach it to
the junction box.

2. Using wire nuts, connect the

power connector to the
household wiring.

3. Plug the power connector into the back of the Alarm.
4. Activate the battery back-up by removing the “Pull to Activate

Battery Back-Up” tab. Or, install battery back-up. Battery back-up
cannot work until you install the battery in the correct position
(Match “+” to “+” and “-” to “-”).

5. Position the base of the Alarm over the mounting bracket, and turn

the Alarm clockwise (right) until the unit is in place. If wall mounted,
adjust unit so words are level.

6. Check all connections.

Improper wiring of the power connector or the wiring leading to
the power connector will cause damage to the Alarm and may
lead to a non-functioning Alarm.

ELECTRICAL SHOCK HAZARD. Do not restore power until all
Alarms are completely installed. Restoring power before installation
is complete may result in serious electrical shock, injury or death.
7. Make sure the Alarm is receiving AC power. Under normal 

operation, the Green power indicator light will shine continuously.

8. If the Green power indicator light does not light, TURN OFF

POWER TO THE JUNCTION BOX

and recheck all connections. 

If all connections are correct and the Green power indicator still
does not light when you restore the power, the unit should be
replaced immediately.

9. Test each Smoke Alarm. Press and hold the Test/Silence button

until the unit alarms. When testing a series of interconnected
units you must test each unit individually. Make sure all units
alarm when each one is tested.

If any unit in the series does not alarm, TURN OFF POWER and
recheck connections. If it does not alarm when you restore
power, replace it immediately.

FOLLOW THESE INSTALLATION STEPS

STAND-ALONE ALARM ONLY:

Connect the white wire on the power connector to the neutral
wire in the junction box.

Connect the black wire on the power connector to the hot wire
in the junction box.

Tuck the orange wire inside the junction box. It is used for 
interconnect only.

INTERCONNECTED UNITS ONLY:
Strip off about 1/2” (12 mm) of the plastic coating on the
orange wire on the power connector.

Connect the white wire on the power connector to the neutral
wire in the junction box.

Connect the black wire on the power connector to the hot wire
in the junction box.

Connect the orange wire on the power connector to the 
interconnect wire in the junction box. Repeat for each unit you 
are interconnecting. Never connect the hot or neutral wires in the
junction box to the orange interconnect wire. Never cross hot
and neutral wires between Alarms.

STAND-ALONE ALARM ONLY:

If you are only installing one Alarm, restore power to the 
junction box.

INTERCONNECTED UNITS ONLY:

If you are interconnecting multiple Alarms, repeat steps 
1-5 for each Alarm in the series. When you are finished,
restore power to the junction box.

Special Requirements For Interconnected Alarms

• Failure to meet any of the above requirements could damage

the units and cause them to malfunction, removing your 
protection.

• AC and AC/DC Alarms can be interconnected. Under AC

power, all units will alarm when one senses smoke or CO.
When power is interrupted, only the AC/DC units in the
series will continue to send and receive signals. AC powered
Alarms will not operate.

Interconnected units can provide earlier warning of fire than stand-alone
units, especially if a fire starts in a remote area of the dwelling. If any unit 
in the series senses smoke, all units will alarm. To determine which Alarm
initiated an alarm, see table:

During an Alarm:

On Initiating Alarm(s)  Red LED(s) flashes (flash) rapidly

On All Other Alarms 

Red LED is Off

After an Alarm (Latching):

On Initiating Alarm(s)

Red LED(s) On for 2 seconds/Off for 2 seconds

On All Other Alarms

Green LED(s) On, Red LED(s) Off

Compatible Interconnected Units

Interconnect units within a single family residence only. Otherwise all
households will experience unwanted alarms when you test any unit 
in the series. Interconnected units will only work if they are wired to 
compatible units and all requirements are met. This unit is designed to
be compatible with: BRK Electronics

®

Smoke Alarm Models 9120,

9120B, SC9120B, 7010, 7010B, 4120, 4120B, 4120SB, 4919, 2002RAC,
100S, 5919, 5919TH; BRK Electronics

®

Heat Alarm Models HD6135F,

HD6135FB; BRK Electronics

®

CO Alarm Models CO5120BN,

CO5120PDBN; Smoke/CO Alarm Model SC6120B, SC7010BV,
SC7010B; and First Alert

®

Smoke Alarm Models SA4120, SA4120B,

SA4121B, SA4919B, SA100B.

Interconnected units must meet ALL of the following requirements:

• A maximum of 18 compatible units may be interconnected 

(Maximum of 12 Smoke Alarms).

• The same fuse or circuit breaker must power all interconnected

units.

• The total length of wire interconnecting the units should be 

less than 1000 feet (300 meters). This type of wire is commonly
available at Hardware and Electrical Supply stores.

• All wiring must conform to all local electrical codes and NFPA 70

(NEC). Refer to NFPA 72, NFPA 101, and/or your local building 
code for further connection requirements.

5

}

A

}

B

8

7

6

3

1

1

2

2

3

4

4

5

A. Unswitched 120VAC 

60 Hz source

B. To additional units; Maximum = 18 total

(Maximum 12 Smoke Alarms)

1. Alarm

2. Ceiling or Wall

3. Power Connector

4. Wire Nut

5. Junction Box

6. Neutral Wire (Wht) 

7. Interconnect Wire

(Orange)

8. Hot Wire (Blk) 

2

3

4

5

INSTALLATION

WHERE TO INSTALL THIS ALARM

Minimum coverage for Smoke Alarms, as recommended by the
National Fire Protection Association (NFPA), is one Smoke Alarm on
every floor, in every sleeping area, and in every bedroom (See
“Regulatory Information For Smoke Alarms” for details on the NFPA 
recommendations).

For CO Alarms, the National Fire Protection Association (NFPA) 
recommends that a CO Alarm should be centrally located outside of
each separate sleeping area in the immediate vicinity of the bedrooms.
For added protection, install additional CO Alarms in each separate 
bedroom, and on every level of your home.

NOTE: For added protection, install an additional Smoke/CO Alarm at 
least 15 feet (4.6 meters) away from the furnace or fuel burning heat
source where possible. In smaller homes or in manufactured homes
where this distance cannot be maintained, install the Alarm as far away
as possible from the furnace or other fuel burning source. Installing the
Alarm closer than 15 feet (4.6 meters) will not harm the Alarm, but may
increase the frequency of unwanted alarms.

In general, install combination Smoke and Carbon Monoxide Alarms:

On every level of your home, including finished attics and basements.

Inside every bedroom, especially if people sleep with the door partly
or completely closed.

In the hall near every sleeping area. If your home has multiple 
sleeping areas, install a unit in each. If a hall is more than 40 feet 
(12 meters) long, install a unit at each end.

At the top of first-to-second floor stairs.

At the bottom of the basement stairs.

For additional coverage, install Alarms in all rooms, halls, and 
storage areas, where temperatures normally remain between 40˚ F
and 100˚ F (4˚ C and 38˚ C).

RECOMMENDED PLACEMENT

When installing on the wall, the top edge of Smoke Alarms should
be placed between 4 inches (102 mm) and 12 inches (305 mm)
from the wall/ceiling line.

When installing on the ceiling, place the alarm as close to the center
as possible.

In either case, install at least 4 inches (102 mm) from where the 
wall and ceiling meet. See “Avoiding Dead Air Spaces” for more
information.

NOTE: For any location, make sure no door or other obstruction could
keep carbon monoxide or smoke from reaching the Alarm.

Installing Smoke/CO Alarms in Mobile Homes
For minimum security install one Smoke/CO Alarm as close to each
sleeping area as possible. For more security, put one unit in each room.
Many older mobile homes (especially those built before 1978) have little
or no insulation. If your mobile home is not well insulated, or if you are
unsure of the amount of insulation, it is important to install units on
inside walls only.

WHERE THIS ALARM SHOULD NOT BE INSTALLED

Do NOT locate this Smoke/CO Alarm:

In garages, furnace rooms, crawl spaces and unfinished attics. 
Avoid extremely dusty, dirty or greasy areas.

Where combustion particles are produced. Combustion particles
form when something burns. Areas to avoid include poorly ventilated
kitchens, garages, and furnace rooms. Keep units at least 20 feet 
(6 meters) from the sources of combustion particles (stove, furnace,
water heater, space heater) if possible. In areas where a 20-foot 
(6 meter) distance is not possible – in modular, mobile, or smaller
homes, for example – it is recommended the Smoke Alarm be
placed as far from these fuel-burning sources as possible. The
placement recommendations are intended to keep these Alarms at
a reasonable distance from a fuel-burning source, and thus reduce
“unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm
is placed directly next to a fuel-burning source. Ventilate these
areas as much as possible.

Within 5 feet (1.5 meters) of any cooking appliance. In air streams
near kitchens. Air currents can draw cooking smoke into the smoke
sensor and cause unwanted alarms.

In extremely humid areas. This Alarm should be at least 10 feet 
(3 meters) from a shower, sauna, humidifier, vaporizer, dishwasher, 
laundry room, utility room, or other source of high humidity.

In direct sunlight.

In turbulent air, like near ceiling fans or open windows. Blowing air
may prevent CO or smoke from reaching the sensors.

In areas where temperature is colder than 40˚ F (4˚ C) or hotter than
100˚ F (38˚ C). These areas include non-airconditioned crawl
spaces, unfinished attics, uninsulated or poorly insulated ceilings,
porches, and garages.

In insect infested areas. Insects can clog the openings to the 
sensing chamber.

Less than 12 inches (305 mm) away from fluorescent lights. 
Electrical “noise” can interfere with the sensor.

In “dead air” spaces. See “Avoiding Dead Air Spaces”.

AVOIDING DEAD AIR SPACES

“Dead air” spaces may prevent smoke from reaching the Smoke/CO
Alarm. To avoid dead air spaces, follow installation recommendations
below.

On ceilings, install Smoke/CO Alarms as close to the center of the 
ceiling as possible. If this is not possible, install the Smoke/CO Alarm 
at least 4 inches (102 mm) from the wall or corner.

For wall mounting (if allowed by building codes), the top edge of
Smoke/CO Alarms should be placed between 4 inches (102 mm) and 
12 inches (305 mm) from the wall/ceiling line, below typical “dead air”
spaces.

On a peaked, gabled, or cathedral ceiling, install first Smoke/CO
Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured 
horizontally. Additional Smoke/CO Alarms may be required depending
on the length, angle, etc. of the ceiling's slope. Refer to NFPA 72 for
details on requirements for sloped or peaked ceilings.

SUGGESTED AREAS FOR INSTALLING 

SMOKE ALARMS, CO ALARMS, AND COMBO UNITS

SMOKE ALARM WITH 
SILENCE FEATURE

CO ALARMS

BOTH, OR COMBINATION 
SMOKE/CO ALARMS

SMOKE ALARMS

KEY:

Suggested locations are based on 
NFPA recommendations (NFPA 72 
for Smoke Alarms and NFPA 720 for 
Carbon Monoxide Alarms). Always 
refer to national and local codes 
before beginning any installation.

In new construction AC and AC/DC smoke alarms MUST 
be interconnected to meet NFPA recommendations.

 

LOCKING FEATURES

The locking features are designed to discourage unauthorized removal of the batteries or Alarm. It is not necessary to activate the locks in 
single-family households where unauthorized battery or Alarm removal is not a concern.

These Alarms have two separate locking features: one to lock the battery compartment, and the other to lock the Alarm
to the mounting bracket. You can choose to use either feature independently, or use them both.

Tools you will need: • Needle-nose pliers  • Standard Flathead screwdriver.

Both locking features use locking pins, which are molded into the mounting bracket. Using needle-nose pliers, remove 
one or both pins from the mounting bracket, depending on how many locking features you want to use.

To permanently remove either lock, insert a flathead screwdriver between the locking pin and the lock, and pry the pin out of the lock.

TO LOCK THE BATTERY COMPARTMENT

Do not lock the battery compartment until you have installed the 
battery and tested the battery back-up.

1. Push and hold Test/Silence button until the alarm sounds.

If the unit does not alarm during testing, DO NOT lock the battery
compartment! Install a new battery and test again. If the Alarm still
does not alarm, replace it immediately.

2. Using needle-nose pliers, detach one locking pin from the mounting

bracket.

3. Push the locking pin through the hole near the battery drawer on 

the back of the Alarm.

TO UNLOCK THE BATTERY COMPARTMENT

Once the Alarm is installed, you must disconnect it from the AC power
before unlocking the battery compartment.

ELECTRICAL SHOCK HAZARD. Turn off the power to the area
where the Alarm is installed before removing it from the mounting
bracket. Failure to turn off the power first may result in serious
electrical shock, injury or death.

Always discharge the branch circuit before servicing an AC or AC/DC
Alarm. First, turn off the AC power at the circuit breaker or fuse box.
Next, remove the battery from Alarms with battery back-up. Finally,
press and hold the Test/Silence button for 5-10 seconds to discharge
the branch circuit.
1. Remove the Alarm from the mounting bracket.

If the unit is locked to the bracket, see the
section “To Unlock the Mounting Bracket.”

2. Disconnect the power connector by gently

prying it away from the back of the Alarm.

3. Insert a flathead screwdriver under the head

of the locking pin, and gently pry it out of the
battery compartment lock. (If you plan to
relock the battery compartment, save the
locking pin.)

4. To relock the battery compartment, close the battery door and 

reinsert locking pin in lock.

5. Reconnect the power connector to the back of the Alarm, reattach

the Smoke Alarm to the mounting bracket, and restore the power.

When replacing the batteries, always test the Alarm before relocking
the battery compartment.

TO UNLOCK THE MOUNTING BRACKET

ELECTRICAL SHOCK HAZARD. Turn off the power to the area
where the Alarm is installed before removing it from the mounting
bracket. Failure to turn off the power first may result in serious
electrical shock, injury or death.

Always discharge the branch circuit before servicing an AC or AC/DC
Alarm. First, turn off the AC power at the circuit breaker or fuse box.
Next, remove the battery from Alarms with battery back-up. Finally,
press and hold the Test/Silence button for 5-10 seconds to discharge
the branch circuit.

1. Insert a flathead screwdriver between the

mounting bracket pin and the mounting
bracket.

2. Pry the Alarm away from the bracket by

turning both the screwdriver and the Alarm
counterclockwise (left) at the same time.

TO LOCK THE MOUNTING BRACKET

1. Using needle-nose pliers, detach one locking pin from mounting

bracket.

2. Insert the locking pin into the lock located

opposite from the battery drawer as shown
in the diagram.

3. When you attach the Alarm to the mounting bracket, the locking

pin’s head will fit into a notch on the bracket.

WHAT YOU WILL SEE AND HEAR WITH THIS ALARM

Under Normal Operations

Voice: Silent

Power/Smoke LED: Constant Green

Horn: Silent

CO LED: Off

When You Test the Alarm

Voice: “Testing.” Horn: 3 beeps, pause, 3 beeps; Voice: “Warning,

evacuate smoke in [Location, example: “Basement”].
Evacuate.”

Power/Smoke LED: Flashes Red in sync with the horn pattern
CO LED: Off,  followed by
Horn: 4 fast beeps, pause, 4 fast beeps;
Voice: “Warning, evacuate carbon monoxide in [Location, example:

“Basement”]. Evacuate.” Pause. “Highest carbon monoxide
level was [CO level example: _0_ ppm]”.

Power/Smoke LED: Off
CO LED: Flashes Red in sync with the horn pattern

If Battery Becomes Low or is Missing

Voice: “Replace battery in [Location, example “Basement”].” 

Repeated every 5 hours

Horn: chirps once a minute
Power/Smoke LED: Flashes Green On for 2 seconds/Off for 

2 seconds. Low Battery Latch is now engaged.

CO LED: Off

If Alarm is Not Operating Properly (MALFUNCTION SIGNAL)

Voice:

“Detector error in [Location, example “Basement”], please
see manual.” Repeated every 5 hours

Horn: 3 chirps every minute
Power/Smoke LED: 3 Flashes approximately once a minute
CO LED: Off

Alarm has reached its End of Life

Voice:

“Detector error in [Location, example “Basement”], please
see manual.” Repeated every 5 hours

Horn: 5 chirps every minute
Power/Smoke LED: 5 Flashes approximately once a minute
CO LED: Off

Alarm Levels of CO are Detected

Horn: 4 fast beeps, pause, 4 fast beeps, pause*
Voice: 
“Warning, evacuate carbon monoxide in [Location, example:

“Basement”]. Evacuate.” Pause. “Highest carbon monoxide
level was [CO level example: ___ ppm]”.

Horn: 4 beeps, pause, 4 beeps, pause repeating 2 times followed 

by Voice Warning above.

Power/Smoke LED: Off
CO LED: During Alarm: Flashes Red in sync with the horn pattern.

After Alarm: Flashes Red On for 2 seconds/Off for 2 
seconds. CO Alarm Latch is now engaged.

*NOTE: If unit goes into CO alarm, the regular 4 beeps-brief pause
cycle will repeat for fifteen minutes. After fifteen minutes, the pause 
will increase to one minute.

Smoke is Detected

Horn:

3 beeps, pause, repeating 8 times

Voice: “Warning, evacuate smoke in [Location, example:

“Basement”]. Evacuate.”

Horn: 3 beeps, pause, repeating 3 times followed by Voice Warning

above.

Power/Smoke LED: During Alarm: Flashes Red in sync with the

horn pattern. After Alarm: Flashes Red On for 2 seconds/Off
for 2 seconds. Smoke Alarm Latch is now engaged.

CO LED: Off

Smoke Alarm is Silenced

Voice:

“Horn silenced.
Detector active.”

Horn: Off
Power/Smoke LED:

Flashes Red

CO LED: Off

CO Alarm is Silenced

Voice:

“Horn silenced.
Detector active.”

Horn: Off
Power/Smoke LED: Off
CO LED: Flashes Red

WEEKLY TESTING

NEVER use an open flame of any kind to test this unit. You
might accidentally damage or set fire to the unit or to your
home. The built-in test switch accurately tests the unit’s
operation as required by Underwriters Laboratories, Inc. (UL).
NEVER use vehicle exhaust! Exhaust may cause permanent
damage and voids your warranty.

If the Alarm ever fails to test properly, replace it immediately.
Products under warranty may be returned to the manufacturer
for replacement. See “Limited Warranty” at the end of this
manual.

It is important to test this unit every week to make
sure it is working properly. Using the test button is
the recommended way to test this Smoke/CO Alarm.
You can test this Smoke/CO Alarm by 
pressing and
holding the Test/Silence button on the Alarm cover until
Alarm Voice says “Testing” (typically 3-5 seconds).

During testing, you will see and hear the following sequence:

• The Alarm Voice will say “Testing.” The Horn will sound 3 beeps,

pause, 3 beeps. The Alarm Voice will say “Warning, evacuate
smoke in [Location, example: “Basement”]. Evacuate.” The
Power/Smoke LED flashes Red and the CO LED will be Off.

• Next the Horn will sound 4 beeps, pause, 4 beeps. The Alarm

Voice will say “Warning, evacuate carbon monoxide in [Location,
example: “Basement”]. Evacuate.” The Power/Smoke LED will
be Off and the CO LED flashes Red.

If the unit does not alarm, make sure the batteries are correctly
installed, and test again. If the unit still does not alarm, replace it
immediately.

2

1

6

REGULAR MAINTENANCE

Use only the replacement batteries listed below. The unit may not
operate properly with other batteries. Never use rechargeable 
batteries since they may not provide a constant charge.

This unit has been designed to be as maintenance-free as possible, but
there are a few simple things you must do to keep it working properly:

Test it at least once a week.

Clean the Smoke/CO Alarm at least once a month; gently vacuum
the outside of the Smoke/CO Alarm using your household vacuum’s
soft brush attachment. Test the Smoke/CO Alarm. Never use water,
cleaners or solvents since they may damage the unit.

If the Smoke/CO Alarm becomes contaminated by excessive dirt,
dust and/or grime, and cannot be cleaned to avoid unwanted
alarms, replace the unit immediately.

Relocate the unit if it sounds frequent unwanted alarms. See
“Where This Alarm Should Not Be Installed” for details.

When the battery back-up becomes weak, the Alarm will “chirp”
about once a minute (the low battery warning), and the Voice will
say “Replace battery in [Location, example “Basement”].” Repeated
every 5 hours. This warning should last 7 days, but you should
replace the battery immediately to continue your protection. 
The Low Battery Latch feature will be engaged. The Green
Power/Smoke LED will flash On for 2 seconds/Off for 2 seconds.

Choosing a replacement battery:

Your Smoke/CO Alarm requires two “AA” Energizer E91 batteries. 
These batteries are available at many local retail stores.

Actual battery service life depends on the Alarm and the environment 
in which it is installed. All the batteries specified above are acceptable
replacement batteries for this unit. Regardless of the manufacturer’s
suggested battery life, you MUST replace the battery immediately
once the unit starts “chirping” (the “low battery warning”).

To replace the batteries (without removing Alarm from the ceiling 
or wall):

1. Open the battery compartment.

2. Press tabs A and B as shown in the 

diagram and remove each battery.

3. Insert the new batteries, making sure

they snap completely into the battery
compartment. Match the terminals on
the ends of the batteries with the 
terminals on the unit.

4. Close the battery compartment, and

then test the unit by pressing the
Test/Silence button.

AB

STEP BY STEP GUIDE TO PROGRAMMING 
THIS ALARM

For First Time and When Changing Batteries

Action:

1. Insert batteries (2, AA batteries).

Alarm Will Say:

“Welcome, First Alert Carbon 
Monoxide and Smoke Alarm.”
“No location programmed” if first
time

or “[Location, example:

“Basement”] location programmed”
when changing batteries.
“To select location, press and
hold test button now.”

2. Press & Hold Test Button if 

you would like to program the
location or change the location
of the Alarm. Release button
after Alarm responds.

“To save location, press and hold
test button after location is
heard.” Alarm will speak list of
locations (see below).

3. After you hear the location of

where you are placing the Alarm,
Press & Hold the Test Button.

“[Location, example: “Basement”]
location saved.”
If no location is chosen: 
“No location saved.”

Your Alarm has now been programmed for the location of your choice.
Available locations:

Basement

Kitchen

Child’s Bedroom

Living Room

Dining Room

Master Bedroom

Family Room

No Location

Guest Bedroom

Office

Hallway

Utility Room

Printed in Mexico
M08-0183-006   K1 09/10

LISTED TO

UL 217 

and

UL 2034

STANDARDS

Summary of Contents for SC7010BV

Page 1: ...Optipath 360 TechnologyTM Two Silence Features Alkaline Battery Backup IMPORTANT PLEASE READ CAREFULLY AND SAVE This user s manual contains important information about your Alarm s operation If you are installing the Alarm for use by others you must leave this manual or a copy of it with the end user Printed in Mexico M08 0183 006 K1 09 10 LISTED TO UL 217 and UL 2034 STANDARDS ...

Page 2: ... 7 If the CO Alarm Sounds 7 If the Smoke Alarm Sounds 7 Using the Silence Features 7 8 Latching Features 8 Smart Interconnect Feature 8 What You Need To Know About CO 8 What is CO 8 Symptoms of CO Poisoning 8 Finding the Source of CO After an Alarm 8 Potential Sources of CO in the Home 8 How Can I Protect My Family From CO Poisoning 9 Regulatory Information For Smoke CO Alarms 9 10 Regulatory Info...

Page 3: ...pread quickly Sources of these fires may include paper burning in a wastebasket or a grease fire in the kitchen Photoelectric technology is generally more sensitive than ionization technology at detecting large particles which tend to be produced in greater amounts by smoldering fires which may smolder for hours before bursting into flame Sources of these fires may include cigarettes burning in co...

Page 4: ...articles are produced Combustion particles form when something burns Areas to avoid include poorly ventilated kitchens garages and furnace rooms Keep units at least 20 feet 6 meters from the sources of combustion particles stove furnace water heater space heater if possible In areas where a 20 foot 6 meter distance is not possible in modular mobile or smaller homes for example it is recommended th...

Page 5: ...king Pins break out of bracket 4 Hot Black AC Wire 5 Neutral White AC Wire 6 Interconnect Orange Wire 7 Quick Connect Power Connector 8 Turn this way to remove from bracket 9 Turn this way to attach to bracket 10 Slide Out Battery Drawer HOW TO INSTALL THIS SMOKE CO ALARM THE PARTS OF THIS ALARM This Smoke CO Alarm is designed to be mounted on any standard wiring junction box up to a 4 inch 10 cm ...

Page 6: ...shine continuously 8 If the Green power indicator light does not light TURN OFF POWER TO THE JUNCTION BOX and recheck all connections If all connections are correct and the Green power indicator still does not light when you restore the power the unit should be replaced immediately 9 Test each Smoke Alarm Press and hold the Test Silence button until the unit alarms When testing a series of interco...

Page 7: ...ies Interconnected units will only work if they are wired to compatible units and all requirements are met This unit is designed to be compatible with BRK Electronics Smoke Alarm Models 9120 9120B SC9120B 7010 7010B 4120 4120B 4120SB 4919 2002RAC 100S 5919 5919TH BRK Electronics Heat Alarm Models HD6135F HD6135FB BRK Electronics CO Alarm Models CO5120BN CO5120PDBN Smoke CO Alarm Model SC6120B SC70...

Page 8: ...rectly installed and test again If the unit still does not alarm replace it immediately 2 1 available at Hardware and Electrical Supply stores All wiring must conform to all local electrical codes and NFPA 70 NEC Refer to NFPA 72 NFPA 101 and or your local building code for further connection requirements 5 A B 8 7 6 3 1 1 2 2 3 4 4 5 A Unswitched 120VAC 60 Hz source B To additional units Maximum ...

Page 9: ...ce a minute CO LED Off Alarm has reached its End of Life Voice Detector error in Location example Basement please see manual Repeated every 5 hours Horn 5 chirps every minute Power Smoke LED 5 Flashes approximately once a minute CO LED Off Alarm Levels of CO are Detected Horn 4 fast beeps pause 4 fast beeps pause Voice Warning evacuate carbon monoxide in Location example Basement Evacuate Pause Hi...

Page 10: ...rom the bracket by turning both the screwdriver and the Alarm counterclockwise left at the same time TO UNLOCK THE BATTERY COMPARTMENT Once the Alarm is installed you must disconnect it from the AC power before unlocking the battery compartment ELECTRICAL SHOCK HAZARD Turn off the power to the area where the Alarm is installed before removing it from the mounting bracket Failure to turn off the po...

Page 11: ...e mounting bracket If the unit is locked to the bracket see the section To Unlock the Mounting Bracket 2 Disconnect the power connector by gently prying it away from the back of the Alarm 3 Insert a flathead screwdriver under the head of the locking pin and gently pry it out of the battery compartment lock If you plan to relock the battery compartment save the locking pin 4 To relock the battery c...

Page 12: ...ttery chirp will resume The Alarm will continue to operate as long as AC power is supplied However replace the batteries as soon as possible to maintain protection in event of a power outage To deactivate this feature Press the Test Silence button again The unit will go into Test Mode and the low battery warning will resume LED flashes and unit sounds chirp once a minute To silence Alarms in an in...

Page 13: ...dren and pets may be the first affected The average healthy adult might not feel any symptoms when the CO Alarm sounds However people with cardiac or respiratory problems infants unborn babies pregnant mothers or elderly people can be more quickly and severely affected by CO If you experience even mild symptoms of CO poisoning consult your doctor immediately FINDING THE SOURCE OF CO AFTER AN ALARM...

Page 14: ...an cause death after 2 hours Standards Underwriters Laboratories Inc Single and Multiple Station carbon monoxide alarms UL2034 According to Underwriters Laboratories Inc UL2034 Section 1 1 2 Carbon monoxide alarms covered by these requirements are intended to respond to the presence of carbon monoxide from sources such as but not limited to exhaust from internal combustion engines abnormal operati...

Page 15: ...mily home townhouse It is recommended this unit be installed on every level of the home in every bedroom and in each bedroom hallway 2 Multi Family or Mixed Occupant Residence Apartment building condominium This unit is suitable for use in individual apartments or condos provided a primary fire detection system already exists to meet fire detection requirements in common areas like lobbies hallway...

Page 16: ...unds for details CO Alarm sounds frequently even though no high levels of CO are revealed in an investigation The CO Alarm may be improperly located Refer to Where to Install This Alarm for details Relocate your Alarm If frequent alarms continue have home rechecked for potential CO problems You may be experiencing an intermittent CO problem Smoke Alarm ONLY Smoke Alarm sounds when no smoke is visi...

Page 17: ...________________________________ Date Installed ____________ ____________Month Year Replace alarm 7 years after installation Please write the date in the space provided _____________ ____________Month Year The alarm will also provide an audible End of Life Signal approximately 7 years after installation to remind you to replace the unit The End of Life Signal can be silenced for up to 2 days Do no...

Reviews: