MAN3184 - TITANUS PRO
•
SENS®
171
9.7 Replacing the filter on special filter
SF-400/650
Figure 105:
Replacing the filter element on the special filter
Perform the following work steps to change the filter element:
► Only perform the following work with the device disconnected from the
mains.
► Loosen the two UPVC transition screw connections 1a on the special
filter and remove.
► Remove the two screw-in plugs on the filter housing.
► Remove the old filter element. Insert the new filter element into the filter
housing.
► Screw the two screw-in plugs into the filter housing.
► Re-place the special filter into the pipe system and fasten it with the
UPVC transition screw connections.
Opening the device cover on the LF-AD-x air filter leads to an airflow fault
on the TITANUS PRO·SENS®.
NOTICE