MAN3184 - TITANUS PRO
•
SENS®
100
Standby current
Minimum capacity of the
backup batteries
Alarm-ready state
In the alarm-ready state, the energy supply must ensure that the backup
batteries are charged and supply the standby current for:
▪ Connected devices
▪ Any connected accessories
To be able to calculate the power supply current
that is actually
required for the alarm-ready state, the standby current
and the charging
current
have to be calculated first.
Standby current [A]
Number of devices
Standby current of device [A]
Number of accessories 2
Standby current/current consumption of accessories 2
Standby current/current consumption of accessories x
Number of accessories x
To be able to calculate the charging current
, the required minimum
capacity of the backup batteries
must be calculated first.
Observe the relevant national laws, standards and directives. For Australia
this is AS 1670.1 Fire detection, warning, control and intercom systems
–
System design, installation and commissioning
– part 1 Fire. In accordance
with these requirements, a hold-up time of 72 h (under certain conditions 24
h) with a subsequent alarm time of 30 min must generally be ensured by the
backup power supply. Deviating hold-up times may be selected for
applications that do not fall under these directives.
Minimum required battery capacity [Ah]
Alarm current [A]
t
1
Required alarm time (0.5 h)
Standby current [A]
t
2
Required hold-up time (30 h)
1.25
Safety factor, only consider for hold-up times <24 h
Summary of Contents for Ampac TITANUS PRO-SENS
Page 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Page 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Page 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Page 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...