MAN3184 - TITANUS PRO
•
SENS®
134
7.3 Aspiration apertures
Figure 83:
Example of a drill hole with aspiration reducing film sheet
Aspiration apertures
Select the type of aspiration aperture and its position in the pipe system
according to project specifications while taking the project planning
guidelines into account.
► Drill a hole with a 10 mm drill at right angles to the pipe.
► Deburr the drill hole carefully and remove any shavings.
► Clean the area around the drill hole (around the whole pipe) from grease
and dust with Tangit cleaner, for instance.
► Select the size of the aspiration reducing film sheet according to the
project planning guidelines.
► Adhere the aspiration reducing film sheet to the drill hole (see the
following figure point "1").
► Ensure the film sheet will not come away. Adhere the sleeve over the
aspiration reducing film sheet (following figure point 2)
The holes in the aspiration reducing film sheet and the sleeve must fit over
the drill hole exactly. The diameter of the opening in the aspiration reducing
film sheet must not be changed.
Carefully avoid touching the film sheet's adhesive surface to ensure it is
kept free of dust and grease.
NOTICE