MAN3184 - TITANUS PRO
•
SENS®
106
► Connect the display circuit board to the basic board.
Connection: X4 (DISPLAY)
► The operating voltage must be reconnected before initialisation. Press
the flow init button on the detector module to initialise the pipe system.
► Close the housing cover.
6.4 Settings
6.4.1 Detector module
Figure 66:
Standard settings on the detector module
6.4.1.1 Response sensitivity setting
The sensitivity of the detector module is generally set using switch S1 (1, 2)
on the TITANUS PRO·SENS® detector module. The following table shows
the response sensitivity (alarm) of the TITANUS PRO·SENS®.
Detector module type
DIL switch S1
DM-TP-50
[% light obscuration/
m]
DM-TP-10
[% light obscuration/
m]
DM-TP-01
[% light obscuration/
m]
Contact 1
Contact 2
-
0.8
0.12
ON
ON
-
0.4
(Standard)
0.06
(Standard)
OFF
ON
1
0.2
0.03
ON
OFF
0.5
(Standard)
0.1
0.015
OFF
OFF
Table 2:
Response sensitivity (main alarm)