MAN3184 - TITANUS PRO
•
SENS®
80
The stubs must be planned based on the previous figure. The I-pipe project
planning configurations shown in the diagram are to be transferred to the
individual aspiration branches of other pipe shapes (U-, M-, double U- and
quadruple U
‑
pipe systems).
For project planning with stubs, it must be ensured that the "critical
length" (lcrit.) of a stub does not exceed the permissible maximum overall
pipe length or branch length (for U-, M-, double U-pipe systems). The
aspiration aperture farthest from the TITANUS PRO·SENS® is referred to as
the critical length. Stubs that are not part of the "critical length" are not added
to the permissible overall pipe length.
A maximum of 2 aspiration apertures can be planned on each stub, whereby
the minimum and maximum distance between the aspiration apertures must
be considered.
Opening diameter
The opening diameters for the planned aspiration apertures according to the
chapter "Opening diameter" apply.
Figure 51:
Opening distances for stubs
Opening distances
The distance between the T-piece and the following stubs as well as the
pipe length between the aspiration apertures on the stubs must not exceed a
maximum of 12 m.
Figure 52:
Maximum stub length
Maximum stub length
The maximum stub length is the pipe length from the last T-piece up to the
last aspiration aperture. All other stubs have to be shorter. A maximum of
2 aspiration apertures may be planned on one stub.
Summary of Contents for Ampac TITANUS PRO-SENS
Page 51: ...MAN3184 TITANUS PRO SENS 51 Figure 34 Pipe shapes...
Page 61: ...MAN3184 TITANUS PRO SENS 61 Figure 36 Example pipe project planning with pipe accessories...
Page 118: ...MAN3184 TITANUS PRO SENS 118 Figure 73 Drill hole intervals for bracket type MT 1 mm...
Page 135: ...MAN3184 TITANUS PRO SENS 135 Figure 84 Attaching the aspiration reducing film sheet...