MAN3184 - TITANUS PRO
•
SENS®
155
8.1.1 Air pressure-independent calibration
Figure 99:
Calibration of the airflow sensor independent of air pressure
► Make sure that the device is in operation for at least 30 min.
► Check the voltage on measuring points MP1 (+) and MP4 (-). Pay
attention to polarity. Select the "V-DC" range on the measuring device.
The voltage at the measuring points is 1.2 V as standard.
► If this is not the case, set the value using trimmer potentiometer R53
with a small screwdriver.
► Press the Flow Init button S2 on the TITANUS PRO·SENS® detector
module.
► Make sure that the display circuit board is connected.
► Close the housing.
No changes may be made to the pipe system after the calibration of the
airflow sensor (section "Airflow sensor calibration"). The airflow sensor must
be recalibrated if subsequent changes are required.
NOTICE