6.4.1.8 Setting the fan voltage of TITANUS PRO·SENS®
Figure 68:
Switching the fan voltage on the basic board
The standard setting for the fan voltage is 6.9 V. In critical areas, the fan
voltage can be switched from 6.9 V to 9 V by unplugging jumper JU1 in
order to increase the transport speed in the pipe system and therefore to
guarantee faster detection in case of greater pipe lengths.
When changing the fan voltage, perform airflow initialisation again. Only
close or open jumper JU1 when the device is switched off.
ATTENTION