GE Multilin
C70 Capacitor Bank Protection and Control System
B-15
APPENDIX B
B.4 MEMORY MAPPING
B
15C8
Direct Outputs Average Message Return Time 1
0 to 65535
ms
1
F001
0
15C9
Direct Outputs Average Message Return Time 2
0 to 65535
ms
1
F001
0
15CA
Direct Inputs/Outputs Unreturned Message Count - Ch. 1
0 to 65535
---
1
F001
0
15CB
Direct Inputs/Outputs Unreturned Message Count - Ch. 2
0 to 65535
---
1
F001
0
15D0
Direct Device States
0 to 65535
---
1
F500
0
15D1
Reserved
0 to 65535
---
1
F001
0
15D2
Direct Inputs/Outputs CRC Fail Count 1
0 to 65535
---
1
F001
0
15D3
Direct Inputs/Outputs CRC Fail Count 2
0 to 65535
---
1
F001
0
Field Unit Input/Output States (Read Only)
15E0
Field Unit Contact Input States (3 items)
0 to 65535
---
1
F500
0
15E3
Field Unit Contact Input Output Operand States (8 items)
0 to 65535
---
1
F500
0
15EB
Field Contact Output Physical States (8 items)
0 to 65535
---
1
F500
0
15F3
Field Contact Output Current States (8 items)
0 to 65535
---
1
F500
0
15FB
Field Contact Output Physical States (8 items)
0 to 65535
---
1
F500
0
1603
Field Shared Input States
0 to 65535
---
1
F500
0
1604
Field Shared Input Channel States
0 to 65535
---
1
F500
0
1605
Field Shared Input Test States
0 to 65535
---
1
F500
0
1606
Field Shared Output Operand States
0 to 65535
---
1
F500
0
1607
Field Latching Output Open Operand States
0 to 65535
---
1
F500
0
1608
Field Latching Output Close Operand States
0 to 65535
---
1
F500
0
1609
Field Latching Output Open Driver States
0 to 65535
---
1
F500
0
160A
Field Latching Output Close Driver States
0 to 65535
---
1
F500
0
160B
Field Latching Output Physical States
0 to 65535
---
1
F500
0
160C
Field Unit Online/Offline States
0 to 65535
---
1
F500
0
160D
Field RTD Input Trouble States
0 to 65535
---
1
F500
0
160E
Field Transducer Input Trouble States
0 to 65535
---
1
F500
0
Ethernet Fibre Channel Status (Read Only)
1610
Ethernet Primary Fibre Channel Status
0 to 2
---
1
F134
0 (Fail)
1611
Ethernet Secondary Fibre Channel Status
0 to 2
---
1
F134
0 (Fail)
1612
Ethernet Tertiary Fibre Channel Status
0 to 2
---
1
F134
0 (Fail)
Data Logger Actual Values (Read Only)
1618
Data Logger Channel Count
0 to 16
channel
1
F001
0
1619
Time of Oldest Available Samples
0 to 4294967295
seconds
1
F050
0
161B
Time of Newest Available Samples
0 to 4294967295
seconds
1
F050
0
161D
Data Logger Duration
0 to 999.9
days
0.1
F001
0
Field Unit RTD Actuals (Read Only) (8 modules)
16C0
Field RTD 1 Value
-32768 to 32767
°C
1
F002
0
16C1
...Repeated for Field RTD 2
16C2
...Repeated for Field RTD 3
16C3
...Repeated for Field RTD 4
16C4
...Repeated for Field RTD 5
16C5
...Repeated for Field RTD 6
16C6
...Repeated for Field RTD 7
16C7
...Repeated for Field RTD 8
Field Unit Transducer Actuals (Read Only) (8 modules)
16C8
Field Transducer 1 Value
-32.768 to 32.767
---
0.001
F004
0
16CA
...Repeated for Field Transducer 2
16CC
...Repeated for Field Transducer 3
16CE
...Repeated for Field Transducer 4
16D0
...Repeated for Field Transducer 5
16D2
...Repeated for Field Transducer 6
16D4
...Repeated for Field Transducer 7
16D6
...Repeated for Field Transducer 8
Table B–10: MODBUS MEMORY MAP (Sheet 7 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...