5-30
C70 Capacitor Bank Protection and Control System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, HTTP, and PRP protocols.
PRP is explained in its own section later.
PRT1 (2 OR 3) IP ADDRESS
: This setting sets the ports IPv4 address in standard IPV4 format. This setting is valid on port 3 if
port 2
REDUNDANCY
is set to None.
PRT1 (2 OR 3) SUBNET MASK
: This setting sets the ports IPv4 subnet mask in standard IPV4 format. This setting is valid on
port 3 if port 2
REDUNDANCY
is set to None.
PRT1 (2 OR 3) GOOSE ENABLED
: This setting enables/disables Goose on the respective port. By default Goose is enabled.
PRT2 REDUNDANCY
determines if ports 2 and 3 operate in redundant or independent mode. If a license for PRP was pur-
chased, the options are None, Failover, and PRP. If a license for PRP was not purchased, the available options are None
and Failover. In non-redundant mode (
REDUNDANCY
set to None), ports 2 and 3 operate independently with their own MAC,
IP, and mask addresses. If
REDUNDANCY
is set to Failover, the operation of ports 2 and 3 is as follows:
•
Ports 2 and 3 use the port 2 MAC address, IP address, and mask
•
The configuration fields for IP address and mask on port 3 are hidden
•
Port 3 is in standby mode and does not actively communicate on the Ethernet network but monitors its link to the Mul-
tilink switch. If port 2 detects a problem with the link, communications is switched to Port 3. Port 3 is, in effect, acting as
a redundant or backup link to the network for port 2. Once port 2 detects that the link between itself and the switch is
good and that communication is healthy for five minutes, then switching back to port 2 is performed. The delay in
switching back ensures that rebooted switching devices connected to the C70, which signal their ports as active prior
to being completely functional, have time to completely initialize themselves and become active. Once port 2 is active
again, port 3 returns to standby mode.
If
REDUNDANCY
is set to PRP, the operation of ports 2 and 3 is as follows:
•
Ports 2 and 3 use the port 2 MAC address, IP address, and mask
•
The configuration fields for IP address and mask on port 3 are overwritten with those from port 2. This is visible on the
front panel but not displayed in the EnerVista software.
•
Port 2
MCST ADDRESS
field is visible
•
The port 2 PTP function still uses only port 2 and the port 3 PTP function still uses only port 3. The relay still synchro-
nizes to whichever port has the best master. When ports 2 and 3 see the same master, as is typically the case for PRP
networks, the port with the better connectivity is used.
NETWORK PORT 2
PRT2 IP ADDRESS:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
PRT2 SUBNET IP MASK:
255.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT2 REDUNDANCY:
None
Range: None, Failover, PRP
None, Failover (if no PRP license)
MESSAGE
PRT2 PRP MCST ADDR:
01-15-4E-00-01-00
Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF
MESSAGE
PRT2 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
NETWORK PORT 3
PRT3 IP ADDRESS:
127.0.0.1
Range: Standard IPV4 address format
MESSAGE
PRT3 SUBNET IP MASK:
255.0.0.0
Range: Standard IPV4 address format
MESSAGE
PRT3 GOOSE ENABLED:
Enabled
Range: Enabled, Disabled
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...