C-10
C70 Capacitor Bank Protection and Control System
GE Multilin
C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE
APPENDIX C
C
2.
Configure the GOOSE service settings by making the following changes in the
PRODUCT SETUP
COMMUNICATION
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
CONFIGURABLE GOOSE
CONFIGU-
RABLE GOOSE 1
settings menu:
–
Set
CONFIG GSE 1 FUNCTION
to “Enabled”.
–
Set
CONFIG GSE 1 ID
to an appropriate descriptive string (the default value is “GOOSEOut_1”).
–
Set
CONFIG GSE 1 DST MAC
to a multicast address (for example, 01 00 00 12 34 56).
–
Set the
CONFIG GSE 1 VLAN PRIORITY
; the default value of “4” is OK for this example.
–
Set the
CONFIG GSE 1 VLAN ID
value; the default value is “0”, but some switches may require this value to be “1”.
–
Set the
CONFIG GSE 1 ETYPE APPID
value. This setting represents the Ethertype application ID and must match the
configuration on the receiver (the default value is “0”).
–
Set the
CONFIG GSE 1 CONFREV
value. This value changes automatically as described in IEC 61850 part 7-2. For
this example it can be left at its default value.
3.
Configure the data by making the following changes in the
PRODUCT SETUP
COMMUNICATION
IEC 61850 PROTO-
COL
GGIO1 STATUS CONFIGURATION
settings menu:
–
Set
GGIO1 INDICATION 1
to a FlexLogic operand used to provide the status of GGIO1.ST.Ind1.stVal (for example, a
contact input, virtual input, a protection element status, etc.).
The C70 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
1.
Configure the reception dataset by making the following changes in the
PRODUCT SETUP
COMMUNICATION
IEC
61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
RECEPTION
CONFIGURABLE GOOSE
CONFIGURABLE GOOSE
1
CONFIG GSE 1 DATASET ITEMS
settings menu:
–
Set
ITEM 1
to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
–
Set
ITEM 2
to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2.
Configure the GOOSE service settings by making the following changes in the
INPUTS/OUTPUTS
REMOTE DEVICES
REMOTE DEVICE 1
settings menu:
–
Set
REMOTE DEVICE 1 ID
to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
–
Set
REMOTE DEVICE 1 ETYPE APPID
to match the Ethertype application ID from the transmitting device. This is “0” in
the example above.
–
Set the
REMOTE DEVICE 1 DATASET
value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3.
Configure the data by making the following changes in the
INPUTS/OUTPUTS
REMOTE INPUTS
REMOTE INPUT 1
settings menu:
–
Set
REMOTE IN 1 DEVICE
to “GOOSEOut_1”.
–
Set
REMOTE IN 1 ITEM
to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
Remote input 1 can now be used in FlexLogic equations or other settings. The C70 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...