C70 Capacitor Bank Protection and Control System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
MESSAGE
CAP 1 TRIP 4:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 TRIP 5:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 TRIP 6:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 SWITCH TO
MANUAL ON TRIP: Yes
Range: Yes, No
MESSAGE
CAP 1 AUTO CTRL EN:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 MAN CTRL EN:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 REMOTE OPEN:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 LOCAL OPEN:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 AUTO OPEN:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 BKR OPEN 52b:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 TRIP SEAL-IN
DELAY: 0.400 s
Range: 0.000 to 60.000 s in steps of 0.001
MESSAGE
CAP 1 REMOTE CLOSE:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 LOCAL CLOSE:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 AUTO CLOSE:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 BKR CLSD 52a:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 DISCHARGE
DELAY: 300 s
Range: 0 to 3600 s in steps of 1
MESSAGE
CAP 1 CLOSE SEAL-IN
DELAY: 0.400 s
Range: 0.000 to 60.000 s in steps of 0.001
MESSAGE
CAP 1 BKR CLOSE BLK:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 CLS OVERRIDE:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 TARGETS:
Disabled
Range: Self-reset, Latched, Disabled
MESSAGE
CAP 1 EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...