5.7 CONTROL ELEMENTS
5 SETTINGS
5
c) BREAKER RESTRIKE
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
BREAKER RESTRIKE 1(3)
One breaker restrike element is provided for each CT bank in the C70.
According to IEEE standard C37.100:
IEEE Standard Definitions for Power Switchgear
, restrike is defined as “a resumption
of current between the contacts of a switching device during an opening operation after an interval of zero current of
¼ cycle at normal frequency or longer”.
Figure 5–108: TYPICAL RESTRIKE WAVEFORM AND DETECTION FLAG
The breaker restrike algorithm responds to a successful interruption of the phase current following a declaration of capaci-
tor bank offline as per the breaker pole indication. If a high-frequency or system frequency current with a magnitude greater
than the threshold is resumed at least ¼ of a cycle later than the phase current interruption, then a breaker restrike condi-
BREAKER RESTRIKE 1
BREAKER RESTRIKE 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BKR RSTR 1 BLOCK:
Off
Range: FlexLogic operand
MESSAGE
BREAKER RESTRIKE 1
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
BREAKER RESTRIKE 1
PICKUP: 0.500 pu
Range: 0.10 to 2.00 pu in steps of 0.01
MESSAGE
BREAKER RESTRIKE 1
RESET DELAY: 0.100 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BREAKER RESTRIKE 1
HF DETECT: Enabled
Range: Disabled, Enabled
MESSAGE
BKR RSTR 1 BKR OPEN:
Off
Range: FlexLogic operand
MESSAGE
BKR RSTR 1 OPEN CMD:
Off
Range: FlexLogic operand
MESSAGE
BKR RSTR 1 CLS CMD:
Off
Range: FlexLogic operand
MESSAGE
BREAKER RESTRIKE 1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
BREAKER RESTRIKE 1
EVENTS: Disabled
Range: Disabled, Enabled
0
2
4
6
8
10
–2
–4
–6
–8
–10
0.01
0.02
0.03
0.05
time (ms)
curr
ent
(amps)
OPERATE
834764A1.CDR
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...