B-34
C70 Capacitor Bank Protection and Control System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
4584
Source 1 Ground CT
0 to 63
---
1
F400
0
4585
Source 1 Phase VT
0 to 63
---
1
F400
0
4586
Source 1 Auxiliary VT
0 to 63
---
1
F400
0
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
25 to 60
Hz
1
F001
60
4601
Phase Rotation
0 to 1
---
1
F106
0 (ABC)
4602
Frequency and Phase Reference
0 to 5
---
1
F167
0 (SRC 1)
4603
Frequency Tracking Function
0 to 1
---
1
F102
1 (Enabled)
Breaker Control (Read/Write Settings) (6 modules)
47D0
Breaker 1 Function
0 to 1
---
1
F102
0 (Disabled)
47D1
Breaker 1 Name
---
---
---
F206
“Bkr 1"
47D4
Breaker 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
47D5
Breaker 1 Open
0 to 4294967295
---
1
F300
0
47D7
Breaker 1 Close
0 to 4294967295
---
1
F300
0
47D9
Breaker 1 Phase A / Three-pole Closed
0 to 4294967295
---
1
F300
0
47DB
Breaker 1 Phase B Closed
0 to 4294967295
---
1
F300
0
47DD
Breaker 1 Phase C Closed
0 to 4294967295
---
1
F300
0
47DF
Breaker 1 External Alarm
0 to 4294967295
---
1
F300
0
47E1
Breaker 1 Alarm Delay
0 to 65.535
s
0.001
F003
0
47E3
Breaker 1 Pushbutton Control
0 to 1
---
1
F102
0 (Disabled)
47E4
Breaker 1 Manual Close Recall Time
0 to 4294967295
s
0.001
F003
0
47E6
Breaker 1 Out of Service
0 to 4294967295
---
1
F300
0
47E8
Breaker 1 Block Open
0 to 4294967295
---
1
F300
0
47EA
Breaker 1 Block Close
0 to 4294967295
---
1
F300
0
47EC
Breaker 1 Phase A / Three-pole Opened
0 to 4294967295
---
1
F300
0
47EE
Breaker 1 Phase B Opened
0 to 4294967295
---
1
F300
0
47F0
Breaker 1 Phase C Opened
0 to 4294967295
---
1
F300
0
47F2
Breaker 1 Operate Time
0 to 65.535
s
0.001
F001
70
47F3
Breaker 1 Events
0 to 1
---
1
F102
0 (Disabled)
47F4
Reserved
0 to 65535
s
1
F001
0
47F5
...Repeated for Breaker 2
481A
...Repeated for Breaker 3
483F
...Repeated for Breaker 4
4864
...Repeated for Breaker 5
4889
...Repeated for Breaker 6
FlexCurves A and B (Read/Write Settings)
4910
FlexCurve A (120 items)
0 to 65535
ms
1
F011
0
4988
FlexCurve B (120 items)
0 to 65535
ms
1
F011
0
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
0 to 65535
---
1
F001
0
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
---
---
---
F202
“ “
4C0A
User-Definable Display 1 Bottom Line Text
---
---
---
F202
“ “
4C14
Modbus Addresses of Display 1 Items (5 items)
0 to 65535
---
1
F001
0
4C19
Reserved (7 items)
---
---
---
F001
0
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
Table B–10: MODBUS MEMORY MAP (Sheet 26 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...